Danger
Incorrect wiring can lead to serious injury from
electrical current and result in appliance dam-
age.
Take the following measures to prevent drifting
of wires into the adjacent voltage area:
■
Route LV leads < 42 V separately from cables
>
42 V/230 V~/400 V~ and secure with cable
ties.
■
Only strip the minimum of insulation from
cables as close as possible to the terminals
and bundle tightly to the corresponding termi-
nals.
■
If 2 components are connected to the same
terminal, press both cores together in a
single
wire ferrule.
Required cable lengths in the heat pump plus wall
clearance
Cable lengths
■
Required cable length inside the appliance plus dis-
tance to wall:
0.5 m
■
Height of wall outlet:
800 mm: See "Technical guide for heat pumps".
Recommended power cables
Power supply
Cable
Max. cable length
Fuse rating
Heat pump control
unit 230 V~
■
Without power-
OFF
3 x 1.5 mm
2
B16 A
■
With power-OFF
5 x 1.5 mm
2
B16 A
Compressor 400 V~
5 x 2.5 mm
2
25 m
B16 A
Instantaneous heating water heater
400 V~
5 x 2.5 mm
2
25 m
B16 A
Installation sequence
Electrical connection
(cont.)
6153640
Installation
Содержание VITOCAL 300-G
Страница 12: ...12 Removing the front panel 3 2 1 4 Fig 3 Installation sequence Siting the heat pump 6153640 Installation...
Страница 14: ...14 5 4 6 Fig 5 7 Fig 6 Installation sequence Siting the heat pump cont 6153640 Installation...
Страница 20: ...20 Opening the wiring chamber 1 2 Fig 10 Installation sequence Electrical connection cont 6153640 Installation...
Страница 22: ...22 6x X X 7 4 8 5 6 Fig 13 10 9 11 Fig 14 Installation sequence Electrical connection cont 6153640 Installation...