47
Terminals
Function
Explanation
X3.12
X3.13
"External demand" signal:
external starting of com-
pressor and pumps; mixer
in control mode or OPEN,
changeover of the operat-
ing status of several system
components
Requires zero volt
N/O
contact:
■ Closed: Demand
■ Open: No demand
■ Breaking capacity 230 V, 2 mA
Note
■ These and further external functions,
such as provision of external set val-
ues, can alternatively be connected via
EA1 external extension.
Installation instructions "EA1
extension"
X3.17
X3.18
MCB/fuse F1 6.3 A (slow)
X3.18
Heat pump control unit
power supply:
Phase L1
X1.1 Earth conductor con-
nection
X2.1 Neutral conductor
connection
Power supply 230 V~
X5/X7
Connections for heat pump
control cable 230 V~
Controller and sensor PCB
Set the required parameters during com-
missioning: See from page 69.
Plug
Sensor/component
Type
F0.1/F0.2
Outside temperature sensor
NTC 10 kΩ
F0.2/F0.3
Radio clock receiver (accessories)
DCF
F4
Buffer temperature sensor
NTC 10 kΩ
F6
(X25.5/
X25.6)
Cylinder temperature sensor, top
NTC 10 kΩ
Installation sequence
Electrical connections, heat pump control unit
(cont.)
5516 436 GB
Installation
Содержание VITOCAL 300-A
Страница 5: ...5 Certificates Declaration of conformity 116 Keyword index 117 Index Index cont 5516 436 GB ...
Страница 79: ...79 8x Troubleshooting Repairs cont 5516 436 GB Service ...
Страница 94: ...94 0011 0010 0009 0008 0004 0005 0006 0007 0001 0003 0002 Parts lists Additional components cont 5516 436 GB ...
Страница 96: ...96 0007 0007 0007 0004 0005 0004 0003 0003 0003 0003 0006 0002 0001 Parts lists Air module cont 5516 436 GB ...
Страница 122: ...122 5516 436 GB ...
Страница 123: ...123 5516 436 GB ...