ACT
Technical water inertial storage tanks
16
6020938-02
To reposition and secure the panel, repeat the process in reverse order.
In a similar way you may access the expansion vessel position, installed on the opposite side.
The side panels may be removed should the need arise to operate on some water connections inside the
unit.
1) Remove the front and rear panels as
indicated above.
Remove the fixing screws of the
indicated side panel.
2) Pull the panel down about
15-20 mm
3) Slide the panel out from the
side
8
START-UP
Before start-up:
•
Make sure that all fasteners are properly tightened and that the feet of the tank are well levelled.
•
Check that all the water connections are properly connected with the appropriate gaskets.
•
Check that all panels are positioned correctly and well-fixed with screws.
CAUTION: IT IS REQUIRED TO REDUCE THE PRESSURE OF THE EXPANSION VESSEL OF THE Vitocal
100-A UNIT TO 1.5 BAR
9
SHUTDOWNS FOR LONG PERIODS
If the unit will not be used for a long period it is suggested to drain the water tank through the appropriate
valve. For the restart, please follow all the instructions and precautions given of this manual.
If the temperature drops below zero there is serious danger of frost: provide a mixture of water
and glycol in the system, otherwise drain the plumbing and the water circuits.
CAUTION: even temporary operation with water temperatures below +5°C is not guaranteed on
the basis of the limits established for the Vitocal 100-A units. Before you turn the unit back on
after a long idle period, make sure that the temperature of the mixture of working fluid is higher
than or at least equal to +5°C.