VITOROND 200
Model
VD2A
125
160
195
230
270
Rated input
(oil)
MBH
490
628
765
902
1059
kW
144
184
224
264
310
Rated input
(gas)
MBH
508
650
792
934
1096
kW
149
190
232
274
321
Rated output
(oil/gas)
†
MBH
433
553
672
792
928
kW
127
162
197
233
273
Combustion efficiency
(oil) %
87.7
87.3
87.3
87.3
87.3
Combustion efficiency
(gas) %
84.7
84.8
84.8
84.8
84.8
Thermal efficiency
(oil) %
87.9
87.6
87.4
87.3
87.2
Thermal efficiency
(gas) %
85.2
85.1
84.8
84.8
84.7
Dimensions
Total Length
inches
35 ¾
42 ¼
49
55
1
/
2
62 ¼
(with insulation
mm
905
1075
1240
1410
1580
jacket)
Total Width*
inches
40
1
/
2
40
1
/
2
40
1
/
2
40
1
/
2
40
1
/
2
mm
1030
1030
1030
1030
1030
Total Height*
††
inches
58
1
/
2
58
1
/
2
58
1
/
2
58
1
/
2
58
1
/
2
mm
1485
1485
1485
1485
1485
Weight
(incl.
lbs
1201
1441
1675
1874
2127
insulation,
kg
545
655
760
850
965
and control)
Boiler water
USG
32
41
49
57
66
content
ltrs
122
154
186
217
249
VITOROND 200
Model
VD2-
320
380
440
500
560
630
Rated input
(oil)
MBH
1255
1490
1726
1961
2196
2471
kW
368
436
506
574
643
724
Rated input
(gas)
MBH
1300
1544
1787
2031
2275
2559
kW
381
452
523
595
666
750
Rated output
(oil/gas)
†
MBH
1110
1319
1526
1732
1941
2183
kW
325
387
447
508
569
640
Combustion efficiency
(oil) %
88.1
88.0
88.0
87.9
87.8
87.8
Combustion efficiency
(gas) %
85.5
85.4
85.4
85.3
85.2
85.1
Thermal efficiency
(oil) %
88.0
88.0
88.0
88.0
88.0
87.9
Thermal efficiency
(gas) %
85.4
85.4
85.4
85.3
85.3
85.3
Total dimensions
Total Length
inches
58 ¾
63 ¾
68 ¾
73 ¾
78 ¾
83 ¾
(with insulation
mm
1490
1620
1750
1870
2000
2130
jacket)
Total Width*
inches
42 ¾
42 ¾
42 ¾
42 ¾
42 ¾
42 ¾
mm
1090
1090
1090
1090
1090
1090
Total Height*
†
inches
58 ¼
58 ¼
58 ¼
58 ¼
58 ¼
58 ¼
mm
1480
1480
1480
1480
1480
1480
Weight
(incl. lbs
3924
4299
4652
4982
5335
5666
insulation, burner
kg
1780
1950
2110
2260
2420
2570
and control)
Boiler water
USG
65
73
80
87
95
102
content
ltrs
247
275
303
331
359
387
Model
VD2-
700
780
860
950
1080
Rated input
(oil)
MBH
2745
3059
3373
3727
4236
kW
804
896
988
1091
1241
Rated input
(gas)
MBH
2843
3168
3493
3860
4387
kW
833
928
1023
1130
1285
Rated output
(oil/gas)
†
MBH
2425
2699
2976
3135
3738
kW
711
791
872
919
1095
Combustion efficiency
(oil) %
87.7
87.6
87.5
87.4
87.3
Combustion efficiency
(gas) %
85.1
85.0
84.9
84.8
84.6
Thermal efficiency
(oil) %
87.9
87.9
87.8
87.8
87.8
Thermal efficiency
(gas) %
85.3
85.2
85.2
85.2
85.2
Total dimensions
Total Length
inches
89.0
93 ¾
98 ¾
104
108 ¾
(with insulation
mm
2260
2380
2510
2640
2760
jacket)
Total Width*
inches
42 ¾
42 ¾
42 ¾
42 ¾
42 ¾
mm
1090
1090
1090
1090
1090
Total Height* inches
58 ¼
58 ¼
58 ¼
58 ¼
58 ¼
mm
1480
1480
1480
1480
1480
Weight
(incl. lbs
6019
6349
6702
7070
7429
insulation, burner
kg
2730
2880
3040
3210
3370
and control)
Boiler water
USG
110
117
124
132
139
content
ltrs
415
443
471
499
527
*Not as illustrated. Boiler control mounted on right or left boiler side panel. †† With supply header.
*Dimensions with center-mounted NR2 control. See Technical Data Manual for dimensions with Dekamatik or KR control.
† Output ratings are based on the IBR BTS-2000 “method to determine efficiency of commercial space heating boilers”.
Содержание VD2 Series
Страница 2: ...Product may not look exactly as illustrated ...
Страница 4: ...Product may not look exactly as illustrated ...
Страница 6: ...Product may not look exactly as illustrated ...
Страница 10: ......