13
Configuring the SDIO/SM1A electronics module for KM-BUS (overview of coding addresses)
Note
Parameter values in
bold
are factory settings.
00 Start temperature differential, solar circuit pump
Display
Value
Explanations
8 K
00:8
... K
00:2 to
00:30
01 Stop temperature differential, solar circuit pump
Display
Value
Explanations
4 K
01:4
... K
01:1 to
01:29
02 Speed control, solar circuit pump
Display
Value
Explanations
Without
02:0
Without speed control
Do not adjust
02:1
With PWM control
02:2
With PWM control
Note
Changed display on Vitotronic 200 heat pump control unit, type WO1C:
"Speed control solar circuit pump"
03 Temperature differential for start of speed control
Display
Value
Explanations
10 K
03:10
... K
03:5 to
03:20
04 Controller amplification of speed control
Display
Value
Explanations
4 %/K
04:4
... %/K
04:1 to
04:10
Controller amplification adjustable from 1 to 10 %/K
05 Min. speed, solar circuit pump
Display
Value
Explanations
10 %
05:10
Min. speed of the solar circuit pump 10 % of max.
speed
... %
05:2 to
05:100
Commissioning
Configuring the SDIO/SM1A electronics module
(cont.)
6131981
Commissioning