System layout 1
The controller calculates the temperature difference bet-
ween collector sensor S1 and tank sensor S2. If the diffe-
rence is larger than or identical to the adjusted switch-on
temperature difference (DT O), the solar pump will be
operated by relay 1, and the tank will be loaded until the
switch-off temperature difference (DT F) or the maximum
tank temperature (S MX) is reached.
Sensors S3 and S4 can optionally be connected for mea-
surement purposes.
R1
Arr 1
S3
1.4 Terminal allocation in the different system layouts
Display Channels
Channel
Description
Terminal
Page
INIT
x*
ODB initialization active
-
37
FLL
x*
ODB filling time active
-
37
STAB
x*
ODB stabilization in progress
-
37
COL
x
Temperature collector
S1
37
TST
x
Temperature tank
S2
37
S3
x
Temperature sensor 3
S3
37
S4
x
Temperature sensor 4
S4
37
TR
x*
Temperature return sensor
S4
37
n %
x
Pump speed R1
R1
38
hP
x
Operating hours R1
R1
38
hP1
x*
Operating hours R1 (if OBST is activated)
R1
38
hP2
x*
Operating hours R2 (if OBST is activated)
R2
38
kWh
x*
Heat quantity kWh
-
38
MWh
x*
Heat quantity MWh
-
38
TIME
x
Time
-
34
If energy metering (OHQM) is activated, sensor S4 has to
be connected as return sensor.
If the drainback option (ODB) is activated, relay 2 can be
used to operate a booster pump by activating the booster
function (OBST).
Note:
Viessmann Vitosol collectors cannot be used in
drainback systems.