background image

13

5603 880  - 01

Pyrot Service & Maintenance

Safety

 Combustion Air Supply

Codes

Provision for combustion and ventilation air must be made 

in accordance with applicable local codes.

In the absence of local codes, use:

CSA B365-10, Installation Code for Solid Fuel Burning 

Appliances and Equipment.

Always use latest edition codes.

WARNING

Failure to provide an adequate supply of fresh combustion 

air can cause poisonous flue gases to enter living space. 

Flue gases entering living space can cause carbon 

monoxide poisoning which can result in severe personal 

injury or loss of life.

WARNING

Never cover the boiler or store debris or other materials 

near the boiler, or in any way block the flow of adequate 

fresh air to the boiler. Never cover the combustion air 

opening. Advise system operator/ultimate owner 

accordingly.

WARNING

The boiler must not be located in areas or rooms where 

chemicals are stored, or aggressive vapors (i.e. bleach, 

hair spray, methyl chloride, carbon tetrachloride or 

perchloroethylene) or high dust levels or humidity levels 

are present. Heat exchanger corrosion might occur and 

reduce the lifetime of the boiler significantly. If above 

criteria are not properly observed and boiler damage 

results, any warranty on the complete boiler and related 

components will be null and void.

General

This equipment requires fresh air for safe operation.

The boiler location must never be under negative pressure. 

Exhaust fans, attic fans, or dryer fans may cause air to be 

exhausted at a rate higher than air can enter the structure 

for safe combustion.

The heating contractor shall ensure all of the following 

requirements are met:

-  An adequate supply of combustion air must be   

 

available to ensure proper combustion.

-  Ambient air temperatures must be maintained within  

 

safe operating limits.

-  When a damper is provided in any opening intended 

 

to admit combustion air into the room within which  

 

the appliance is installed, the damper shall be 

     interlocked to prevent any boiler from starting 

 

before the damper is fully open.

-  Each duct used to convey air from the outdoors 

 shall 

have:

 

1.  a cross-sectional area throughout its length at 

 

     least equal to the free area of the inlet and outlet  

 

     openings which it connects,

 

2.  making a provision for outside combustion air, 

 

     the intake shall not be less than 1 ft. (0.3 m)  

 

     above the anticipated snow level for the location.

-  The heating contractor must check with local    

 

authorities (municipal building department) for 

     combustion air requirements particular to the area.
See “Installation and Operating Instructions” for more 

details.

Содержание KRT 150 series

Страница 1: ... property damage personal injury or loss of life Improper installation adjustment and or operation could cause carbon monoxide poisoning resulting in injury or loss of life This product must be installed and serviced by a professional service technician who is experienced and qualified in hot water boiler installation and wood fuel combustion Do not store or use gasoline or other flammable fluids ...

Страница 2: ...ulatory and Installation Requirements Contaminated air Air contaminated by chemicals can cause by products in the combustion process which are poisonous to inhabitants and destructive to Viessmann equipment For a listing of chemicals which cannot be stored in or near the boiler room please see subsection entitled Mechanical Room Advice to owner Once the installation work is complete the heating co...

Страница 3: ...h serious injury or substantial product property damage Indicates an imminently hazardous situation which if not avoided may result in minor injury or product property damage Helpful hints for installation operation or maintenance which pertain to the product This symbol indicates to note additional information This symbol indicates that other instructions must be referenced Note Viessmann Manufac...

Страница 4: ...iler 15 Heat exchanger displacement rods 16 Installing the displacement rods 16 Removing the displacement rods 16 Flue gas cyclone optional 17 Pneumatic cleaning system optional 17 Feed systems 18 Shutdown 19 Boiler 19 Extraction and conveyance systems 19 Control system 19 Replacing the buffer battery 19 Ash disposal 19 Disposal of the boiler 19 Instructions regarding removal 19 Waste disposal 19 ...

Страница 5: ...and Boilers CSA B365 10 Installation Code for Solid Fuel Burning Appliances and Equipment Viessmann solid fuel boiler can only be installed and serviced by qualified trained personnel Steel wood fired hot water heating boiler For operation primarily with modulating boiler water temperatures in closed loop forced circulation hot water heating systems Under certain conditions open loop systems may a...

Страница 6: ...er where the literature can be found Contact Viessmann for additional copies This product comes with several safety instruction labels attached Do not remove Contact Viessmann immediately if replacement labels are required Please carefully read this manual prior to attempting service and maintenance Any warranty is null and void if these instructions are not followed For information regarding othe...

Страница 7: ...vironmentally friendly operation The build up of soot on the heat exchanger raises the flue gas temperature and reduces efficiency IMPORTANT Keep boiler and boiler room clear and free of combustible materials gasoline and other flammable vapors and liquids Do not obstruct the flow of combustion and ventilation air All inspection maintenance and service must be performed by a qualified heating cont...

Страница 8: ... in moving parts and noise Power supply 120V or 240V 1 and 208V 3 60Hz In case of an emergency the Pyrot can be disconnected from the electrical power supply at all the leads by the main switch on the control cabinet CAUTION FIRE HAZARD The boiler must NEVER be operated with the doors open Any burning bits that escape could start a fire RISK OF INJURY If the doors are open during operation sparks ...

Страница 9: ...ing contractor Check pressure gage for correct system water pressure Check for water on the floor from the discharge pipe of the pressure relief valve or any other pipe pipe joint valve or air vent Check for moisture water or appearance of rust on the flue gas pipes their joints as well as vent dampers or side wall vent terminals if so equipped Ensure that nothing is obstructing the flow of combus...

Страница 10: ...for an extended period of time during cold weather water pipes may freeze and burst resulting in extensive water damage and conditions in which mold could grow Certain molds are known to cause respiratory problems as well as to pose other serious health risks In case of water damage immediate measures should be taken to dry out affected areas as quickly as possible to prevent mold from developing ...

Страница 11: ...rm water after handling Suppliers of ceramic fiber products recommend the following first aid measures Respiratory tract nose and throat irritation If respiratory tract irritation develops move the person to a dust free location Eye irritation If eyes become irritated flush immediately with large amounts of lukewarm water for at least 15 minutes Eyelids should be held away from the eyeball to ensu...

Страница 12: ...cturing plants Photo processing plants Beauty salons Products containing contaminants Chlorine type bleaches detergents and cleaning solvents found in household laundry rooms Paint and varnish removers Hydrochloric acid muriatic acid Chlorine based swimming pool chemicals Spray cans containing chlorofluorocarbons Chlorinated waxes and cleaners Cements and glues Refrigerant leaks Calcium chloride u...

Страница 13: ...observed and boiler damage results any warranty on the complete boiler and related components will be null and void General This equipment requires fresh air for safe operation The boiler location must never be under negative pressure Exhaust fans attic fans or dryer fans may cause air to be exhausted at a rate higher than air can enter the structure for safe combustion The heating contractor shal...

Страница 14: ...e ashing system optional 5 Igniter 6 Controlled combustion air supply system 7 Rotary blower Viessmann patented 8 Boiler door 9 Heat exchanger qP Rotary combustion chamber Viessmann patented qQ Safety heat exchanger for thermal safety flush valve qW Frequency controlled flue gas exhaust blower qE Pneumatic cleaning system optional qR Flue gas recirculation pipe Maintenance ...

Страница 15: ...e absolutely sure to turn OFF the main switch CAUTION RISK OF INJURY Shut the system off before starting any cleaning Be absolutely sure to wear protective gloves protective eyewear if required and use the cleaning tools that come with the system danger of blow ups burns and getting crushed CAUTION After approx 1000 operating hours Clean the recirculated flue gas line After approx 300 operating ho...

Страница 16: ...d the displacement rods can be easily removed Removing the displacement rods RISK OF INJURY Shut the system off before starting any cleaning Be absolutely sure to wear protective gloves protective eyewear if required and use the cleaning tools that come with the system danger of blow ups burns and getting crushed CAUTION Heat exchanger displacement rods The displacement rods improve the heat trans...

Страница 17: ...m or wire brush After every cleaning of the boiler heat exchanger Open the side lids and clean the guide blades of the cyclone with a hand brush Check the level of the ash container regularly and empty the bin before it is completly full Never operate the boiler without an ash bin IMPORTANT Pneumatic cleaning system optional Operation and maintenance of the air compressor optional according to the...

Страница 18: ...S Lubricate the gasket between the extraction casing and the geared motor and universal joint for the auger If a fuel hopper is installed do not alter equipment in any way May be connected to an existing boiler or solar system RISK OF INJURY Shut the system off before starting any cleaning Be absolutely sure to wear protective gloves protective eyewear if required and use the cleaning tools that c...

Страница 19: ...d the service life of the buffer battery Replacing the buffer battery The buffer battery is built in beneath the removable lid on the control module type Panasonic Lithium BR2330 It is for buffering the time date and settings Note The battery needs replacing every five years DO NOT disconnect the main power or turn off the main switch while changing the battery Ash disposal Ashes should be stored ...

Страница 20: ...ance Boiler re establishes its performance Boiler reestablishes its performance Boiler re establishes its performance Residual oxygen ACTUAL Residual oxygen TARGET Fuel W35 Open primary air vent Check that grate vents move smoothly Contact Viessmann 1 Clean grate 2 Clean all four sight glasses and pipes of the ember monitoring system light barrier 3 Check the position of the light barrier F3 param...

Страница 21: ...od and of the bronze bearing by means of grease removers Check grate for foreign material Are all grate components properly inserted Lateral play sliding grate for the concrete 3 16 1 32 5 1 mm applies up to KRT 300 5 16 1 16 8 2 mm applies up to KRT 400 540 Crank axle distance KRT 100 150 1e 35 mm KRT 220 300 25 32 55 mm KRT 400 540 35 32 80 mm Setting stop position sliding grate back crank drive...

Страница 22: ...the back of the fireclay can be seen in the substructure Checking for increased wear of fireclay Check the recirculation system Check damper Check fireclay for discoloration Cleaning in the area of the arch in the chimney and in the area of the opening of the shut off valve Recirculation must be hot at partial load Damper must be installed Damper must not be fully open chimney draft may be too str...

Страница 23: ...heck guide tube for deformation possible cause of deformation Overheating If there is increased wear of the fireclay perform check see section checking for increased wear of Fireclay Check guide tube for wear Seal must fit properly and be caulked Procedure if a seal is leaking Replace ceramic packing of the seal check by means of impression test that the whole surface of the seal lies on the ceram...

Страница 24: ...he boiler Clean the outside of the oxygen sensor using a wire brush Hold the oxygen sensor downwards and gently tap out with the bristles of the wire brush until no more dirt falls out of the probe Check that all electrical lines are permanently connected Balance the oxygen sensor see section on balancing the oxygen sensor Set the heating system to cleaning Check the leak tightness of the installa...

Страница 25: ... the air without contact to metal Measure the oxygen sensor signal Boiler status off Balance the oxygen sensor Install the oxygen sensor The oxygen sensor must be supplied with a heating voltage in the range between 13 0 and 13 8V measured at the white white wires The heating voltage can be adjusted on the main board The signal voltage must be in the range between 6 and 11 mV measured at the grey ...

Страница 26: ...tion chamber filling time is too short Use suitable dry fuel Readjust oxygen sensor Replace ignition device Readjust combustion chamber Acknowledge with OK 20 Water level in extinguishing Water container red light at F3 Level float switch in extinguishing water container Not enough water in the extinguishing water container Fill extinguishing water container Acknowledge with OK 25 Light barrier em...

Страница 27: ...5 Conveyor device red light at F4 Maintenance cover limit switch One of the maintenance covers is open or not closed properly Check and close all the maintenance covers Acknowledge with OK 51 52 Extraction system red light at F4 Maintenance cover limit switch One of the maintenance covers is open or not closed properly Check and close all the maintenance covers Acknowledge with OK 53 54 Extraction...

Страница 28: ...essmann Manufacturing Company U S Inc 45 Access Road Warwick Rhode Island 02886 USA 1 800 288 0667 Fax 401 732 0590 www viessmann us com info viessmann us com Viessmann Manufacturing Company Inc 750 McMurray Road Waterloo Ontario N2V 2G5 Canada 1 800 387 7373 Fax 519 885 0887 www viessmann ca info viessmann ca Pyrot Service Maintenance ...

Отзывы: