background image

Safety and Installation Requirements

Please ensure that these instructions are read and understood before commencing installation. Failure to comply

with the

instructions listed below can cause

product/property damage

,

severe personal injury

, and/or

loss of life

.

Working on the equipment

The installation, adjustment, service,
and maintenance of this product must
be done by a

licensed professional

heating contractor

who is qualified and

experienced in the installation, service,
and maintenance of hot water boilers.
There are no user serviceable parts on
the boiler, burner, or control.

Ensure

main power

supply to

equipment, the heating system, and all
external controls has been

deactivated

.

Close main oil supply valve

. Take

precautions in both instances to avoid
accidental activation of power during
service work.

Ensure that the installation
literature of other applicable
components is referenced.

General Information

Standard installation

Boiler
Model

VR1

-22

-27

-33

Rear

Sides

Flue

inches
mm
inches
mm
inches
mm

6

150

0
0
1

25

6

150

0
0
1

25

6

150

0
0
1

25

Floor

Combustibles

Alcove installation

Boiler
Model

VR1

-22

-27

-33

Rear

Sides

Flue

Top*

inches
mm
inches
mm
inches
mm
inches
mm

6

150

0
0
1

25

6

150

6

150

0
0
1

25

6

150

6

150

0
0
1

25

6

150

Floor

Combustibles

* 24” with Vitotronic control.

The insulated oil direct vent system is
rated for a 1” clearance to
combustibles.

Advise owner to keep direct vent
termination and air intake free of
debris, snow and ice.

NOTE: Surface discoloration on the
outside of the building may occur if the
burner is not properly adjusted.
Viessmann will not accept any
responsibility for such discoloration.

NOTE: Direct Vent exhaust system
operates under a positive pressure
developed by the burner. Make sure all
vent connections and observation port
on the boiler are sealed air-tight by
tightening screws and using high
temperature silicone sealant if
necessary.

NOTE: The vent components must be
supplied without any alteration except
for the length of the flex pipe to be cut
to the desired length.

P

le

a

s

e

fi

le

in

S

e

r

v

ic

e

B

in

d

e

r

5351 050 v2.5 09/2012

Installation Instructions
Supplement

for use by heating contractor

Direct Vent Systems

,

Part No. Z005 875 (FDVS-4)

for Vitorond 100 boilers

IMPORTANT

Viessmann will not assume any
responsibility for possible effects of
an obstructed air intake or exhaust
termination.

WARNING

Содержание FDVS-4

Страница 1: ...lcove installation Boiler Model VR1 22 27 33 Rear Sides Flue Top inches mm inches mm inches mm inches mm 6 150 0 0 1 25 6 150 6 150 0 0 1 25 6 150 6 150 0 0 1 25 6 150 Floor Combustibles 24 with Vitotronic control The insulated oil direct vent system is rated for a 1 clearance to combustibles Advise owner to keep direct vent termination and air intake free of debris snow and ice NOTE Surface disco...

Страница 2: ...g system when using the flexible insulated stainless steel oil vent The direct vent kit includes a VRV 4 vacuum relief valve which must be installed in the air intake pipe as close as possible to the burner when using a Beckett burner see Fig 1 The direct vent kit includes a Viessmann specific stainless steel boiler to vent transition adaptor Do not install the regular galvanized vent pipe adaptor...

Страница 3: ... a constant 120 VAC power source supplied to the BLACK wire on the control see wiring diagram on following page 1 The cover mounting plate is not a conduit connection point Pass conduit and attached connector through the front opening in the mounting plate or through one of the knockouts on either side of the cover and attach it directly to the burner mounted 4x4 electrical junction box Room therm...

Страница 4: ...ass 1 If original wire as supplied with boiler must be replaced type 105 C wire or equivalent must be used Supply wiring to boiler and additional control wiring must be 14 ga or heavier Provide electrical ground at boiler as required by codes Burner wiring harness supplied Fig 3 5351 050 v2 5 Electric shock hazard Can cause severe personal injury or loss of life if power source including service s...

Страница 5: ...h limit control see wiring diagram below Fig 4 Legend Oil solenoid valve Ignition transformer Burner motor CAD cell flame detector Burner grounding screw R7184 Series primary control with post purge factory default setting 30 sec can be field adjusted see Beckett burner manual Factory installed jumper 5351 050 v2 5 Electric shock hazard Can cause severe personal injury or loss of life if power sou...

Страница 6: ... cut off must be provided as required by local codes Connect incoming line voltage HOT L1 wire to terminal L1 and N to terminal L2 of the Honeywell high limit control see wiring diagram below Fig 5 5351 050 v2 5 Electric shock hazard Can cause severe personal injury or loss of life if power source including service switch on boiler is not disconnected before installing or servicing WARNING Ensure ...

Страница 7: ...r off delay post purge factory default settings can be field adjusted requires a constant 120 VAC power source supplied to the BLACK wire on the control see wiring diagram on page 9 1 The cover mounting plate is not a conduit connection point Pass conduit and attached connector through the front opening in the mounting plate or through one of the knockouts on either side of the cover and attach it...

Страница 8: ... wall away from influences of drafts hot or cold water pipes lighting fixtures television sun rays or fireplaces 2 Follow instructions supplied with room thermostat If it has a heat anticipator set heat anticipator in thermostat to match power requirements of equipment connected to it Boiler wiring diagrams give setting for standard equipment 5351 050 v2 5 ...

Страница 9: ... control wiring must be 14 ga or heavier Provide electrical ground at boiler as required by codes 5351 050 v2 5 Electric shock hazard Can cause severe personal injury or loss of life if power source including service switch on boiler is not disconnected before installing or servicing WARNING Jumper RED Viessmann 41 plug control connection BL O BK W G R B4 S3 T2 T1 N G L1 18 Blue Closed end connect...

Страница 10: ...ing service switch on boiler is not disconnected before installing or servicing WARNING Blue and orange wires not used in this application DO NOT cut or remove closed end connector from the wires 120 VAC power supply installer must provide 15A overcurrent protection Main ON OFF switch field supplied Low water cut off if required field supplied G L1 T1 T2 N S3 B4 BK W G R Y Y O BL W V BK R BL O T T...

Страница 11: ... supplied with boiler must be replaced type 105 C wire or equivalent must be used Supply wiring to boiler and additional control wiring must be 14 ga or heavier Provide electrical ground at boiler as required by codes 5351 050 v2 5 Electric shock hazard Can cause severe personal injury or loss of life if power source including service switch on boiler is not disconnected before installing or servi...

Страница 12: ... harness see wiring diagram on page 12 Cable strap supplied Honeywell high limit control Burner wiring 1 Secure control harness using 2 supplied cable straps Room thermostat wiring 1 Install thermostat on inside wall away from influences of drafts hot or cold water pipes lighting fixtures television sun rays or fireplaces 2 Follow instructions supplied with room thermostat If it has a heat anticip...

Страница 13: ...105 C wire or equivalent must be used Supply wiring to boiler and additional control wiring must be 14 ga or heavier Provide electrical ground at boiler as required by codes Burner wiring harness supplied Fig 11 If Beckett burner is being installed cut this length to 6 for connection to burner junction box located under the burner primary control 5351 050 v2 5 Electric shock hazard Can cause sever...

Страница 14: ...nect incoming line voltage HOT L1 wire to terminal L1 and N to terminal L2 of the Honeywell high limit control see wiring diagram below Post purge timer setting in conjunction with Honeywell Aquastat Model L7248C1006 If Err4 fault occurs set post purge timer to a maximum of 45 seconds Exceeding 45 seconds may lead to LED error code Err4 on the older version of the Honeywell Aquastat 5351 050 v2 5 ...

Страница 15: ...ostat wiring 1 Install thermostat on inside wall away from influences of drafts hot or cold water pipes lighting fixtures television sun rays or fireplaces 2 Follow instructions supplied with room thermostat If it has a heat anticipator set heat anticipator in thermostat to match power requirements of equipment connected to it Boiler wiring diagrams give setting for standard equipment Electrical c...

Страница 16: ...at boiler as required by codes 5351 050 v2 5 Electric shock hazard Can cause severe personal injury or loss of life if power source including service switch on boiler is not disconnected before installing or servicing WARNING Jumper RED Viessmann 41 plug control connection BL O BK W G R B4 S3 T2 T1 N G L1 18 Blue Closed end connectors are factory installed on RED ORANGE and BLUE wires These RED OR...

Страница 17: ...BR W W BK R GY W BL BK Air pressure switch R R NC NO G L1 T1 T2 N S3 B4 BL O G BRN BL W W O BK R G Riello burner sub base Factory installed jumper R G W BK BL O 41 1 2 41 1 2 2 Blue wire not used in this application DO NOT cut or remove closed end connector from the wire Power supply Provide disconnect means and overload protection as required Control case must be connected to earth ground 120 VAC...

Страница 18: ... n a Oil nozzle Delavan 0 50x60 B n a 0 75x60 A W Hago 0 50x60 B 0 60x60 B n a Oil nozzle flow rate GPH psig 0 65 190 0 75 175 1 00 175 Air tube length inches mm 7 178 7 178 7 178 Air tube insertion inches mm 3 83 3 83 35 8 92 Air tube combination NX70LP NX70LP NX70LJ Head type 6 slot 6 slot 9 slot Head setting 2 00 2 50 3 25 Air setting see head setting Static plate n a Baffle n a Fuel pump 21844...

Страница 19: ...65 175 0 75 175 1 00 140 Air tube length inches mm 7 178 7 178 65 16 160 Air tube insertion inches mm 45 8 118 45 8 118 4 108 Turbulator setting 0 0 1 0 1 0 Air gate setting 3 7 5 0 4 0 1 For VR1 27 boiler replace installed nozzle with nozzle packaged with Riello burner 2 Factory installed nozzle 3 Nozzles must be installed by installer Note Riello oil burners are factory set for Vitorond 100 VR1 ...

Страница 20: ...20 5351 050 v2 5 Technical information subject to change without notice Printed on environmentally friendly recycled and recyclable paper 5351 050 v2 5 ...