23
C
B
A
Fig. 16
1.
Danger
Escaping gas leads to a risk of explosion.
Close the gas shut-off valve.
Undo fitting
A
on the gas supply pipe.
2.
Undo the screws on the boiler door and open the
door.
3.
Check the wire mesh of burner gauze assembly
B
and thermal protection ring
C
for damage. Slight
wavy deformations of burner gauze assembly
B
are OK.
4.
If required, replace burner gauze assembly
B
together with thermal protection ring
C
.
Installation instructions
Replacing burner components
Checking the ignition electrodes and ionisation electrode
Ignition electrodes
7
0.5
+ -
3.5
0.5
+
-
5
1
+ -
Fig. 17
Ionisation electrode
12
2
±
Fig. 18
Check ignition electrodes and ionisation electrode for
correct gap to the burner gauze assembly and for pos-
sible damage. Replace electrodes if required.
Installation instructions
Replacing burner components
Commissioning, inspection, maintenance
Checking the burner gauze assembly