12
Conversion for 87 kW
F
C
D
E
A
B
Fig. 3
0
1.
Close the gas shut-off valve.
0
2.
Turn off the system ON/OFF switch at the user
interface of the control unit.
0
3.
Switch OFF the mains isolator (outside the instal-
lation room) or isolate the mains power and
secure against unintentional reconnection.
0
4.
Undo fitting
A
.
0
5.
Release gas train
B
from flange
C
.
0
6.
Remove restrictor
D
with O-ring
E
from flange
C
.
0
7.
Secure gas train with O-ring
E
to flange
C
.
Restrictor
D
is no longer required.
0
8.
Secure fitting
A
.
0
9.
Where present for set gas type: Affix label "Set
to ..."
F
supplied over the existing label.
10.
Check control cables:
■
Correct connection and kink-free routing
■
Application and seating of retaining clips
11.
Start the burner.
12.
Check for gas tightness.
Danger
Escaping gas leads to a risk of explosion.
Check gas routing components for leaks.
!
Please note
The use of leak detection spray can result in
faulty operation.
Leak detection spray must not come into
contact with electrical contacts.
Commissioning, inspection, maintenance
Converting to natural gas LL
(cont.)
5812086