Troubleshooting
Faults indicated in the "Faults" menu
(cont.)
Cause:
The room temperature is too low to
ensure frost protection
Result:
The control unit creates a heat
demand
Remedy:
Check system components
Cause:
At least one boiler is in a fault state
(multi-boiler control unit)
Result:
Output possibly too low
Remedy:
Check the boiler (see VitodensĂ200
service instructions)
Cause:
Communication error
Remedy:
Check KM BUS connection
Cause:
Communication error
Remedy:
Check BUS connection
Cause:
Faulty
BUS user
2
Remedy:
See VitotronicĂ050 service
instructions
Sensor resistance table
Temp-
erature
[
º
C]
Resis-
tance
[
W
]
Temp-
erature
[
º
C]
Resis-
tance
[
W
]
Temp-
erature
[
º
C]
Resis-
tance
[
W
]
Temp-
erature
[
º
C]
Resis-
tance
[
W
]
ć15 36
Ă
475
15 7
Ă
885
45 2
Ă
185
75
739
ć10 27
Ă
665
20 6
Ă
245
50 1
Ă
801
80
627
ć5 21
Ă
166
25 5
Ă
000
55 1
Ă
493
85
535
0 16
Ă
325
30 4
Ă
028
60 1
Ă
244
90
457
5 12
Ă
695
35 3
Ă
265
65 1
Ă
041
95
393
10 9
Ă
995
40 2
Ă
663
70
876
100
339
5862Ă474ĂGB
Frost prot. room
Boiler
error code:
Boiler comm.
Comm. 2-wire BUS
2Ćwire BUS
E2