Hydraulic connection, coolant (from industrial waste heat)
Note
The max. inlet temperature for water/water heat pumps
is 20 °C. At higher coolant temperatures, a low end
controller (on site) must limit the inlet temperature.
Note
The separating heat exchanger must be resistant to
the substances contained in the coolant.
RL
VL
RL
A
B
C
D
K
H
G
E
F
Fig. 16
A
Overflow
B
Inlet
C
Dirt filter (on site)
D
Low end controller and valve (on site)
E
Primary pump
F
To the heat pump
G
Separating heat exchanger, primary circuit
H
Circulation pump (
≙
well pump)
K
Water container
(min. 3000 l capacity, on site)
Hydraulic connection, heating water buffer cylinder
P
M
M
MASTER
S
Fig. 17
Preparing for installation
Hydraulic connection requirements
(cont.)
5855865
Installation