49
A
Compressor
Change with
MIN
0
Code 1
MAX
255
B
D
C
E
G
Output
Compressor stage
5030 :
Del con 0
17
F
Fig. 23
A
Parameter group
B
Parameter description
C
Parameter code
D
Currently set value
E
Upper limit of the setting range
F
Identification of the delivered condition
G
Lower limit of the setting range
Note
The limits of setting range
E
and
G
and delivered
condition
F
depend on which parameter has been
selected. The values are displayed for almost all
parameters in the heat pump control unit. Conse-
quently values
E
,
F
and
G
are not listed in the fol-
lowing parameter descriptions.
Bit field
Bit fields are used to specify the combination of sev-
eral functions or system components with
1 parame-
ter
. For any combination,
precisely 1
setting value
results.
The setting value of the parameter can be determined
in accordance with the following table:
Setting example
Bit
Settings for any parameter
Bit signifi-
cance
Setting combination
0: Not selected
1: Selected
Total
Bit 1
Setting 1
1
1
1
Bit 2
Setting 2
2
0
0
Bit 3
Setting 3
4
0
0
Bit 4
Setting 4
8
0
0
Bit 5
Setting 5
16
1
16
Bit 6
Setting 6
32
1
32
...
...
...
0
0
Bit N
...
2
N
–
1
0
0
Parameter setting value
"49"
Setting wizard
With the setting wizard, Bit 0 to Bit N can be selected
from a list (multiple selections are possible). The set-
ting value of a parameter results automatically from the
selected combination.
Note
Assignment of bits to system components or functions:
See the description of the relevant parameter.
1. Service menu and Coding level 1 are enabled.
The required parameter group has been selec-
ted:
Select parameter with bit field: E.g.
"Enable use
of compressor stage 5012"
.
Control unit settings
Setting parameters
5800 917 GB
Parameter