66
Heating mode
■
Weather-compensated operation:
The rooms are heated in accordance with the room
temperature settings.
The control unit determines a set flow temperature
for the heat generator, subject to the outside temper-
ature, the room temperature and the slope/level of
the heating curve.
■
Room temperature-dependent operation (con-
stant operation with room thermostat):
System with one heating circuit without mixer. The
rooms are heated in accordance with the settings of
the room temperature controller/room thermostat
(accessories).
If the room temperature controller/room thermostat
issues a demand, the standard set flow temperature
is maintained. If there is no demand, the frost protec-
tion function is active.
■
Constant operation without room thermostat:
The rooms are heated according to the set flow tem-
perature settings.
Heating curve
The heating curves represent the relationship between
the outside temperature and the flow temperature.
Simplified: The lower the outside temperature, the
higher the flow temperature must be in order to reach
the set room temperature.
Factory settings:
■
Slope = 1.4
■
Level = 0
0.2
Outside temperature in °C
Boiler
water
or
flow temperature
in °C
Slope
2.4
2.6
2.8
3.0
3.2
3.4
90
80
70
60
50
40
30
0
-5 -10 -15 -20
5
10
2.0
2.2
Set room temperature
in °C
35
30
25
20
15
10
5
0.4
0.6
0.8
1.0
1.2
1.4
-30
-25
1.8
1.6
Fig. 32
Slope setting ranges:
■
Underfloor heating systems: 0.2 to 0.8
■
Low temperature heating systems: 0.8 to 1.6
Set room temperature
Standard room temperature
Individually adjustable for each heating circuit.
Function description
Appliance functions
6174240
Functions