54
Example: to configure the motorised flue
gas damper (flue gas cascade), press
the following keys:
1. S
longer than 2 s,
" "
flashes.
2.
until "6" is shown under Serv-
ice.
3. S
"6" is shown under Status and
"1" under Service.
4.
until "7" is shown under Serv-
ice.
5. S
"7" will be displayed under Sta-
tus.
6. /
until "1" appears under Service
to link the motorised flue gas
damper.
7. S
to confirm. If applied success-
fully, "1" will be shown under
Service; if it failed, "0" will
appear.
8. S
to change to the operating dis-
play.
Reset all operating parameters to their delivered condition
To reset all operating parameters to their
delivered condition, press the following
keys:
1. S
longer than 2 s,
" "
flashes.
2.
until "6" is shown under Service.
3. S
"6" will be displayed under Sta-
tus.
4.
until "0" is shown under Service.
5. S
"1" is shown under Status and
"dEL" under Service.
6. S
to confirm. If reset successfully,
"1" will be shown under Service; if
it failed, "0" will appear.
7. S
to change to the operating dis-
play.
Manual mode and service display
The burner must be running to call up the
service display and for manual mode.
The service display shows the current
modulation level in %.
Press the following keys:
1.
/
S
simultaneously for longer than
2 s.
The burner changes to manual
mode, a "P" will be shown
under Status and the current
modulation level will flash
under Service.
Burner control unit
Burner control unit
(cont.)
5794 780 GB