Supply pressure (flow pressure)
Action
Natural gas
LPG
Below 10 mbar
(1.0 kPa)
Below 15 mbar
(1.5 kPa)
Make no adjustments and notify your local
gas supply utility.
10 to 15 mbar
(1.0 to
1.5 kPa)
15 to 20 mbar (1.5 to
2.0 kPa)
Temporary mode in order to maintain heating
operation. Not for permanent operation.
15 to 35 mbar
(1.5 to
3.5 kPa)
20 to 35 mbar (2.0 to
3.5 kPa)
Start the boiler
Above 35 mbar
(3.5 kPa)
Above 35 mbar
(3.5 kPa)
Notify your local gas supply utility in order to
have the pressure reduced. Pressure at the
boiler valve must not exceed 50 mbar
(5.0 kPa).