41
A
AVI PCB (see page 51)
F101 Fuse 1.0A (slow)
B
Control module and power supply
for instantaneous heating water
heater
C
Luster terminals (see page 48)
F1 Fuse 6.3 A (slow)
D
Controller and sensor PCB (see
page 50)
E
Main PCB (see page 41)
F3 Fuse 6.3 A (slow)
F
Extension PCB on main PCB (see
page 44)
G
Programming unit
Main PCB (operating components 230 V~)
Information regarding the connection
values
■ The output given is the recommended
connected load.
■ The total output of all components con-
nected directly to the heat pump con-
trol unit must not exceed 1000 W (e.g.
pumps, valves, message facilities,
contactors).
If the total output < 1000 W, the indi-
vidual rating of a component (e.g.
pump, valve, message facility, contac-
tor) can be greater than specified.
However, never exceed the breaking
capacity of the corresponding relay.
■ The stated current indicates the max.
switching current of the switching con-
tact (observe the total current of 5 A).
■ Safety LV is unsuitable for controlling
external heat sources.
Set the required parameters during com-
missioning; see from page 74.
Plug
sYA
Terminals
Function
Explanation
211.5
AC
Type AWB-AC:
Cooling control
3-way diverter valves for
heating water buffer cylinder
bypass in cooling mode
Connection values
■ Max. output: 10 W
■ Voltage: 230 V~
■ Max. switching current: 4(2) A
Connect the 3-way diverter valves for the
bypass circuit in parallel.
Installation sequence
Electrical connections
(cont.)
5601 429 GB
Installation
Содержание 7424689
Страница 83: ...83 Opening the programming unit 1 3 2 2x Troubleshooting Repairs 5601 429 GB Service ...
Страница 84: ...84 Removing cover from programming unit if necessary 5 4 4x Troubleshooting Repairs cont 5601 429 GB ...
Страница 85: ...85 Placing the control panel in its service position 4x 2 3 1 Troubleshooting Repairs cont 5601 429 GB Service ...
Страница 86: ...86 Removing the separating plate 1 2 Troubleshooting Repairs cont 5601 429 GB ...