Viega Hydronic Mixing Block User Guide

UG-HC 566234 0720 Hydronic Mixing Block

Wiring

Connecting to the Wiring 

Terminal Block

All wiring shall be done through the wiring 

terminal block. The wiring terminal block has 9 

terminals and should be connected as follows:

 

Terminal 1,2 - Thermostat or end switch 

(terminal 1 and 2 can accept a dry contact or 

24v powered contact).

 

Terminal 3,4 - Outdoor Sensor.

 

Terminal 4,5 - Boiler Sensor.

 

Terminal 6,7 - Boiler Contact (TT) relay rated 

for 24V AC 1.0 Max AMPS.

 

Terminal 8,9 - Internal relay rated for 24V AC 

1.0 Max Amps. With the addition of a pump 

and boiler relay this contact can be used for 

low head primary loop pump control. 

Plug cord into 120V AC - standard wall outlet 

(altering the cord will void the warranty).

End Switch from Zone 

Control or Thermostat 

(Dry or Powered contact)

Pump 

and 

Boiler 

Relay

120 VAC

Power

Supply

Primary Loop 

Pump P1

24

VAC

Com

Boiler Sensor 

S1

Boiler

Hydr

onic Mixing Block

Содержание Hydronic Mixing Block

Страница 1: ...TION Only suitably qualified individuals with formal training in electrical and HVAC controls should attempt the installation of this equipment Incorrect wiring and installation will affect the warran...

Страница 2: ...l using the four screw mounting holes Level the backplate A Hydronic Mixing Block mounting holes B Backplate mounting holes 7 Slide the Hydronic Mixing Block into the backplate The backplate will slid...

Страница 3: ...iping from the manifold The branch connection on the Return Fitting fitting 2 should connect to the return tee on the primary loop 3 Connect the Delivery Fitting fitting 3 to the supply piping to the...

Страница 4: ...ntact Terminal 3 4 Outdoor Sensor Terminal 4 5 Boiler Sensor Terminal 6 7 Boiler Contact TT relay rated for 24V AC 1 0 Max AMPS Terminal 8 9 Internal relay rated for 24V AC 1 0 Max Amps With the addit...

Страница 5: ...for this configuration Legend Thermostat Low Voltage Line Voltage Hydronic Mixing Block Terminal 1 2 3 3 0 8 1 2 Three Wire Thermostat Wiring schematic for part numbers 15116 15117 and 15118 1 Connect...

Страница 6: ...iring schematic for part number 18050 1 Connect R from the transformer to the R terminal on the thermostat 2 Connect C from the transformer to C terminal on the thermostat 3 Connect W terminal on the...

Страница 7: ...tdoor Sensor to a wall with the wiring entering either through the back or bottom of the enclosure Do not mount the Outdoor Sensor with the conduit knockout facing upwards as rain could enter the encl...

Страница 8: ...center spacing Install minimum of 6 pipe diameters of straight pipe upstream and downstream of all closely spaced tees Differential pressure bypass valve prevents flow noise under partial load conditi...

Страница 9: ...ower cables If the sensor wires are located in an area with strong sources of electromagnetic interference EMI shielded cable or twisted pair should be used or the wires can be run in a grounded metal...

Страница 10: ...color that reflects the current status The user can navigate the menus after the power on sequence is complete Programming Setup Menu The SETUP MENU is used for entering the design values as well as a...

Страница 11: ...ion is not available with BOILER AQUASTAT mode OPERATION CONSTANT The circulator is constantly on and will only be shut off with warm weather shut down WWSD Usually used with RESET mode Circulator Set...

Страница 12: ...FIXED The control will maintain a constant FIXED water temperature WATER TEMP The fixed water temperature Range 50 F to 180 F Default 120 F TEMP CONTROL RESET Water temperature will adjust based on ou...

Страница 13: ...peratures This setting will allow the boiler to go above the boiler target by half of this setting Example if the BOILER DIFF is set at 20 F the boiler will run until the temperature is 10 F above the...

Страница 14: ...them in the Settings Template and User Selections on page 16 RESTORE DEFAULTS Restores the current Default Settings If the Factory Default Settings were overwritten the User Settings selected during t...

Страница 15: ...ing Block supplies This symbol present in the field means the sensor is bad or the wire is broken or shorted OUTDOOR The outdoor temperature as read by the outdoor sensor PRESSURE The system pressure...

Страница 16: ...180 F Default 120 F NA NA Reset MIX DESIGN NA Range 50 F to 180 F Default 120 F NA Reset MIX MIN NA Range 50 F to 180 F Default 70 F NA BOILER SETTINGS TYPE Default RESET RESET CONDENSING AQUASTAT Not...

Страница 17: ...low for purging If more time is needed ACTIVATE may be selected as many times as necessary to complete system purging If less time is needed purge can be cancelled by selecting CANCEL 8 Allow the Hydr...

Страница 18: ...0 120 49 3 760 15 26 139 402 125 52 3 383 10 23 118 018 130 54 3 050 5 21 100 221 135 57 2 754 0 18 85 362 140 60 2 490 5 15 72 918 145 63 2 255 10 12 62 465 150 66 2 045 15 9 53 658 155 68 1 857 20 7...

Страница 19: ...19 of 20 Viega Hydronic Mixing Block User Guide UG HC 566234 0720 Hydronic Mixing Block...

Страница 20: ...Viega LLC 585 Interlocken Blvd Broomfield CO 80021 Phone 800 976 9819 www viega us Viega Hydronic Mixing Block User Guide UG HC 566234 0720 Hydronic Mixing Block...

Отзывы: