Cut the pipe properly using a pipe cutter or fine-toothed hacksaw.
Avoid grooves on the pipe surface.
3.2.3
Pressing the connection
NOTICE!
Leaky press connections due to pipes being too short
If two press connectors are to be mounted onto a pipe
without an interval, the pipe must not be too short. If the
pipe is not inserted up to the prescribed insertion depth in
the press connector during pressing, the connection may
become leaky.
With pipes with a diameter of d 15–28 mm, the length of the
pipe must be at least as long as the total insertion depth of
both press connectors.
Requirements:
n
The pipe end is not bent or damaged.
n
The pipe is deburred.
n
The correct sealing element is in the press connector.
EPDM = polished black
n
The sealing element is undamaged.
n
The complete sealing element is in the bead.
Push the press connector onto the pipe as far as it will go.
Handling