Strip 8 mm of the single cores.
Plug the single cores in the respective slot at an angle of approx.

45°.

NOTICE! 

Connecting the connection plug to the control too soon will

damage the flushing station.
At this step, do not connect the connection plug to the con‐

trol.

3.2.3

Switching on

The binary inputs of the BMS module must only be controlled from the

building automation via potential-free NO contacts.
The binary outputs of the BMS module (relay contact / NO contact) con‐

trol the inputs of the building automation potential-free, max.

24 V / 100 mA.

3.3

Commissioning

3.3.1

Commissioning the BMS module in a new system

Commissioning of the flushing station is completed.

n

Carry out commissioning of the flushing station, see instructions for

the flushing station.

Put the plug in the yellow socket.
Establish the connection to the control.
Call up the web application.
Activate the BMS module in the configuration menu.
Refresh the page.

ð

The 

„BMS module“

 appears on the left.

Handling

BMS module binary

11 from  12

Содержание 2241.68

Страница 1: ...For flushing stations with Viega Hygiene function Model Year built 2241 68 from 11 2017 en_INT BMS module binary Instructions for Use...

Страница 2: ...BMS module binary 2 from 12...

Страница 3: ...2 Product description 6 2 2 1 Overview 6 2 2 2 Technical data 7 3 Handling 8 3 1 Assembly information 8 3 1 1 Required material and tools 8 3 2 Assembly 8 3 2 1 Mounting the BMS module on the basic ho...

Страница 4: ...riction does not extend to possible operating instructions The installation of Viega products must take place in accordance with the general rules of engineering and the Viega instructions for use 1 2...

Страница 5: ...or in Germany e g DIN DVGW Some passages in the text may refer to technical codes in Europe Germany These should serve as recommendations in the absence of corresponding national regulations The rele...

Страница 6: ...table exclusively for flushing stations with Viega Hygiene function models 2241 10 and 2241 20 For detailed installation instructions refer to the instructions for use for the flushing station 2 2 Pro...

Страница 7: ...ng binary inputs and binary outputs of building auto mation n connection adapter n Splash water protected IP54 n 8 inputs signals from building automation potential free n 12 outputs signals for build...

Страница 8: ...tionally the clamp type terminals are colour coded alternately The twelve binary outputs of the BMS module are marked O1 to O12 Addi tionally the clamp type terminals are colour coded alternately Rem...

Страница 9: ...of the mounting holes Drill the mounting holes bore diameter 3 mm Use the self tapping screws to fasten the BMS module on the basic holder system Mounting with self tapping screws Handling BMS module...

Страница 10: ...e Unscrew the cable screw connection Remove the protective plug Screw the connection on Insert the connection cable max 14 x 2 x 0 8 single core max 0 8 mm approx 0 5 mm2 Tighten the cable screw conne...

Страница 11: ...ts The binary outputs of the BMS module relay contact NO contact con trol the inputs of the building automation potential free max 24 V 100 mA 3 3 Commissioning 3 3 1 Commissioning the BMS module in a...

Страница 12: ...non ferrous metals and dispose of in accordance with valid national legal requirements Electronic components and batteries must not be put in the domestic waste but must be disposed of appropriately i...

Отзывы: