2.3.3
Technical data
Operating voltage
24 V AC
Max. wattage
max. 50 W
Switching voltage pump
230 V
Switching current pump
5 A
Fuse
T 2A
Max. no. of room thermostats
6
Max. no. of actuators
12
Heating programs - optional
2
Protection class
II
Degree of protection
IP20
CE conformity
EN 60730
Ambient temperature
0–60 °C
Storage temperature range
-25–65 °C
Relative humidity – non-condensing
≤
80 %
Dimensions H / W / D
75 / 40 / 325 mm
Weight
350 g
Usable line cross-sections (terminals)
1.5 mm
2
(solid line)
2.3.4
Accessories
Electrically operated valve for regulating the heating water volume flow
in the heating circuit.
Actuator
"
closed in de-energised state
"
, 24 V – model 1249.1
Actuator
Fig. 4: Actuator
Product information
Basic unit 24 V
with pump module
8 from 17
Содержание 1247.4
Страница 2: ...Basic unit 24 V with pump module 2 from 17...