How to parameter a XT for arming/disarming with any master system supplying 9-12 V
DC
or a dry contact ?
XTENDER mode should be set up during the panel initial configuration.
ARMING PROFILE :
FROM THE HOST
MODE SLOW
: The panel will arm each device
one at a time saving battery life. This mode is
recommended
.
MODE FAST
: The panel will arm all devices at the
same time. This mode increases significantly the
battery consumption.
OK or YES
to choose the parameter
.
ENTRY DELAY
VALUE (0-255) :
(000) : _
Enter the value for your Entry Delay up to 255
seconds and press
OK or YES.
Note : In From the Host mode, the entry/exit delay
are dealt by the master system.
TRANSMISSION DELAY
VALUE (0-600) :
(000) : _
ARMING CONFIRMATION
VALUE (0-240) :
(0) : _
Arming Confirmation is the number of seconds the
system will wait to arm after voltage is latched on
the arming input. This feature can be used as an
exit delay, we suggest you to enter the same value
as your master system exit delay.
Enter the value you would like for the Arming
Confirmation and press
OK or YES
.
OK
or
YES
ARMING MODE
MODE :
SLOW
MODE :
FAST
OK
or
YES
OK
or
YES
OK
or
YES
The transmission delay value set the delay between
the detection of an event and its transmission to the
monitoring center.
Except when specifically required, please enter 0.
Enter the value you would like for the Transmission
Delay and press
OK or YES.