How to parameter a XT for arming/disarming with any master system supplying 9-12 V

DC

 or a dry contact ?

 

XTENDER mode should be set up during the panel initial configuration.

ARMING PROFILE :

FROM THE HOST

MODE SLOW

 : The panel will arm each device 

one at a time saving battery life. This mode is 

recommended

.

MODE FAST

 : The panel will arm all devices at the 

same time. This mode increases significantly the 

battery consumption.

OK or YES

 to choose the parameter

.

ENTRY DELAY

VALUE (0-255) :

(000) : _

Enter the value for your Entry Delay up to 255 

seconds and press  

OK or YES. 

Note : In From the Host mode, the entry/exit delay 

are dealt by the master system.

TRANSMISSION DELAY

VALUE (0-600) :

(000) : _

ARMING CONFIRMATION

VALUE (0-240) :

(0) : _

Arming Confirmation is the number of seconds the 

system will wait to arm after voltage is latched on 

the arming input.  This feature can be used as an 

exit delay, we suggest you to enter the same value 

as your master system exit delay.

Enter the value you would like for the Arming 

Confirmation and press  

OK or YES

.

OK 

or 

YES

ARMING MODE

MODE :

SLOW

MODE :

FAST

OK 

or 

YES

OK 

or 

YES

OK 

or 

YES

The transmission delay value set the delay between 

the detection of an event and its transmission to the 

monitoring center.

Except when specifically required, please enter 0.

Enter the value you would like for the Transmission 

Delay and press 

OK or YES.

www.videofied.com

3

A P P L I C A T I O N   N O T E

www.videofied.com

2. Arming and disarming from 9-12 V

DC

3

Содержание XT

Страница 1: ... Host Panel 1 Introduction Page 2 2 Arming and disarming from 9 12 VDC Page 3 2 1 Master system with external 12 VDC Page 4 2 2 Master system with dry contact Page 4 3 Arming and disarming from a XT master system Page 5 Index www videofied com 1 Doc Ref 240 XT Version March 2014 ...

Страница 2: ...ote describes how to set up the XT panel for XTENDER use The XT panels used in XTENDER or used as master system must be powered by an AC power supply When the XT panel is used in XTENDER mode the system will only be able to arm and disarm by latching 9 12 VDC to its arming inputs Arming Input 1 and or Arming Input 2 When voltage is 0V the panel automatically disarms If the XT is used as a master s...

Страница 3: ...master system TRANSMISSION DELAY VALUE 0 600 000 _ ARMING CONFIRMATION VALUE 0 240 0 _ Arming Confirmation is the number of seconds the system will wait to arm after voltage is latched on the arming input This feature can be used as an exit delay we suggest you to enter the same value as your master system exit delay Enter the value you would like for the Arming Confirmation and press OK or YES OK...

Страница 4: ...em with 12 V DC Contact 220V AC XT Panel Prog Out Com PWR AC2 DC Arming Input 2 Ref Prog Input 3 Ref GND Prog Output 1 Prog Output 2 Prog Input 1 Prog Input 2 Ref GND Arming Input 1 Ref PWR AC1 DC L N AC DC Master System with dry contact 220V AC Arming Inputs In XTENDER mode the system devices are divided into two partitions Those partitions are controlled either by Arming Input 1 or Arming Input ...

Страница 5: ...C2 DC Arming Input 2 Ref Prog Input 3 Ref GND Prog Output 1 Prog Output 2 Prog Input 1 Prog Input 2 Ref GND Arming Input 1 Ref PWR AC1 DC XT Slave Panel XT Master Panel Prog Out Com PWR AC2 DC Arming Input 2 Ref Prog Input 3 Ref GND Prog Output 1 Prog Output 2 Prog Input 1 Prog Input 2 Ref GND Arming Input 1 Ref PWR AC1 DC Arming Disarming Impulse Relay AC DC NOTE You can confirm the arming of the...

Отзывы: