Victron & Pylontech US2000B and Phantom-S

Victron Energy - https://www.victronenergy.com/live/

This parameters page is also a good place to check that all batteries are connected and working
properly. In normal working conditions, the current limit is 25A per cell. For example, 75A charge
current limit ( 75 / 25 = 3 ) means there are 3 Pylontech battery modules connected.

6. VE-Direct MPPT Settings

In normal operation the MPPT charge characteristics are governed by the 

Venus-device

 via DVCC,

with instructions from the connected Pylontech battery.

This section presumes familiarity with 

VictronConnect

The settings below are a precautionary measure.

MPPT Parameter Setting
Battery voltage.

48V

Absorption voltage 53V

7. Example Wiring Diagram

Содержание Pylontech Phantom-S

Страница 1: ... Victron Venus device and can support multiple battery modules connected in parallel 1 Product system compatibility Battery US2000B US2000B Plus US3000 Plus Module capacity 2 4 kWh 2 4 kWh 3 5 kWh 1 1 Offgrid Backup and Energy Storage Systems are possible Victron Pylontech can be used for the following system types Off grid Grid Backup Energy Storage Systems Self Consumption ESS Start page 1 2 A Ven...

Страница 2: ...Venus device to regulate charge currents as the batteries require due to temperature etc To test operation try disconnecting the Venus device from the MPPT After a time out the MPPT will stop charging and flash an error code on its LEDs The error code is error 67 no BMS MPPTs with a VE Can port Use of VE Can MPPT s with Pylontech batteries is not supported or documented 2 Minimum Battery Sizing Rec...

Страница 3: ...40 100 100 8000 20000 7 8400 33600 Quattro 48 15000 200 100 100 12000 25000 10 12000 48000 3 CAN bus Wiring You can connect multiple battery modules together to form a single large battery by connecting the RJ 45 cable supplied by Pylontech using the link ports on the battery This is shown in more detail in the example wiring diagram and Pylontech manual The batteries will automatically detect and...

Страница 4: ...ngs changes on other devices if they depend on the power supply from the battery Without this connection the battery may turn off unexpectedly 4 VEConfigure Settings You will need the latest firmware on all connected devices This section presumes familiarity with VEConfigure software 4 1 General tab Check the Enable battery monitor function Set the battery capacity to the total capacity of the battery...

Страница 5: ...are specific to the Pylontech battery in the VEConfigure ESS Assistant are below Select the externally managed Lithium battery option ESS Parameter Settings Sustain voltage 48V Dynamic cut off values set all values to 46V Restart offset 1 2V Default Due to the reliability of the grid supply and the behaviour of the sustain voltage threshold in ESS you may wish to suppress the low voltage pre alarm war...

Страница 6: ...Limit 102A for 15 seconds 200A for 0 1 seconds and 400A short circuit current If operation is attempted outside the operating range the battery will disconnect to protect itself 5 Venus device Settings On the Venus device go to Settings System setup Venus Settings System Setup Parameter Value DVCC ON Shared Voltage Sense OFF Select the CAN bus BMS 500 kbit s CAN profile in the CCGX Menu path Settin...

Страница 7: ...r cell For example 75A charge current limit 75 25 3 means there are 3 Pylontech battery modules connected 6 VE Direct MPPT Settings In normal operation the MPPT charge characteristics are governed by the Venus device via DVCC with instructions from the connected Pylontech battery This section presumes familiarity with VictronConnect The settings below are a precautionary measure MPPT Parameter Set...

Страница 8: ...these steps Step 0 If the Inverter Charger or Venus device does not switch on As a safety precaution the inverter charger will not switch on if the Venus device is not on If you are unable to start the system due to a total system blackout battery shutdown due to low voltage you may need to disconnect the VE BUS connection cable between the inverter charger and Venus device You can then start the ...

Страница 9: ... system is up and running LEDs are on Step 2 Check that the Pylontech battery is ready for use Check the Max Charge Voltage parameter This voltage parameter is sent together with the other three parameters by the Pylontech system via the CAN bus cable They are visible on the Venus device Device List Pylontech battery Parameters menu Step 3 Check the Pylontech manual The Pylontech manual contains a...

Страница 10: ...ttery This happens with new batteries and after a deep discharge 10 Further Information For information about where to buy or find suitably qualified installers visit the Where to Buy Page Further community discussion about installing and using Pylontech and Victron can found at Victron Community use the topic label Pylontech DISQUS View the discussion thread From https www victronenergy com live Vi...

Отзывы: