Inverter RS Smart

ENGLISH

Содержание RS Smart

Страница 1: ...Inverter RS Smart ENGLISH ...

Страница 2: ...sholds adjustable in VictronConnect 14 5 2 3 High battery voltage 15 5 2 4 High temperature 15 6 Troubleshooting and Support 16 6 1 Error Codes 16 6 1 1 Error 2 Battery voltage too high 16 6 1 2 Error 3 Err 4 Remote temperature sensor failure 16 6 1 3 Error 5 Remote temperature sensor failure connection lost 16 6 1 4 Error 6 Error 7 Remote battery voltage sense failure 16 6 1 5 Error 8 Remote batt...

Страница 3: ...8 6 1 24 Error 114 CPU temperature too high 18 6 1 25 Error 116 Calibration data lost 18 6 1 26 Error 119 Settings data lost 19 6 1 27 Error 121 Tester fail 19 7 Warranty 20 8 Technical Specifications 21 9 Appendix 23 9 1 Appendix A Connection Overview 23 9 2 Appendix B Block Diagram 25 9 3 Appendix C Example Wiring Diagram 25 9 4 Appendix D Dimensions 26 Inverter RS Smart ...

Страница 4: ...least 196 strands class 5 or higher stranding according to VDE 0295 IEC 60228 and BS6360 An AWG2 gauge cable should have at least 259 26 stranding 259 strands of AWG26 Maximum operating temperature 90 C Example of suitable cable class 5 Tri rated cable it has three approvals American UL Canadian CSA and British BS In case of thicker strands the contact area will be too small and the resulting high...

Страница 5: ...nd check that the ventilation vents are not blocked Installation of this product must in a location that restricts access by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety The connections to live parts s...

Страница 6: ... smartphones tablets or other compatible devices No additional dongle or accessory required VE Direct port and two VE Can ports Either communications port type can be used for a wired data connection to a GX device e g Cerbo GX Color Control GX PC or other devices Note that only one port can be used at a time Device Display A 4 line LCD back lit display shows operational information including batt...

Страница 7: ...rder to prevent overcharging of the battery After a deep discharge the absorption time is automatically increased to make sure that the battery is completely recharged Additionally the absorption period is also ended when the charge current decreases to less than 2A Float During this stage float voltage is applied to the battery to maintain a fully charged state Optional external voltage and tempe...

Страница 8: ... Excessively high ambient temperature will result in the following Reduced service life Reduced charging current Reduced peak capacity or shutdown of the inverter Never position the appliance directly above lead acid batteries The Inverter RS is suitable for wall mounting For mounting purposes a hook and two holes are provided at the back of the casing The device must be fitted vertically for opti...

Страница 9: ...ave synchronising PV solar inverters can be connected to the AC output see section on Frequency Shift Function for more information The is a safety class I product supplied with a ground terminal for safety purposes Its AC output terminals and or grounding point on the outside of the product must be provided with an uninterruptible grounding point for safety purposes The is provided with a ground ...

Страница 10: ...e cable losses during charging two sense wires can be connected directly to the battery or to the positive and negative distribution points Use wire with a cross section of 0 75mm During battery charging the charger will compensate the voltage drop over the DC cables up to a maximum of 1 Volt i e 1V over the positive connection and 1V over the negative connection If the voltage drop threatens to b...

Страница 11: ... auxiliary input 1 positive connection 4 AUX_IN2 Programmable auxiliary input 2 positive connection 5 REMOTE_L Remote on off connector Low 6 REMOTE_H Remote on off connector High 7 RELAY_NC Programmable relay Normally Closed connection 8 RELAY_COM Programmable relay common negative 9 TSENSE Temperature Sensor negative 10 TSENSE Temperature Sensor positive 11 VSENSE Voltage Sensor negative 12 VENSE...

Страница 12: ...ter to appear in the device list in the Local or the VRM tab Click on the inverter In case of a connection via Bluetooth Enter the default PIN code 000000 After entering the default PIN code VictronConnect will ask you to change the PIN code This is to prevent unauthorized connections in the future It is recommended that you change the PIN code on first install This can be done in the product info...

Страница 13: ...ect with adaptive absorption time or fixed absorption time will be used Both are better explained below Fixed absorption time The same length of absorption is applied every day when there is enough solar power by using the maximum absorption time setting Be aware that this option can result in overcharging your batteries especially for lead batteries and system with shallow daily discharges See yo...

Страница 14: ...y and also to prevent stratification of the electrolyte in flooded batteries Whether automatic equalization is necessary or not depends on the type of batteries and their usage Consult your battery supplier for guidelines When the Automatic equalization cycle has initiated the charger applies an equalization voltage to the battery as long as the current level stays below the equalization current p...

Страница 15: ...equired by Lithium batteries For Lithium Iron Phosphate batteries this setting is preset at 5 degrees Celsius for the other battery types it is disabled When creating a user defined battery the cut off temperature level can be adjusted manually Manual Equalization Start now Selecting Start now on Manual equalisation allows manual initiation of an Equalization cycle To allow the charger to equalize...

Страница 16: ...ency adjustment While no further configuration is required it is important that the AC PV inverter is configured correctly to respond to the frequency adjustment by reducing its output Note the 1 1 rule of AC PV inverter size to inverter size and minimum battery sizing applies More information about these limitations are available in the AC Coupling manual and this document is required reading if ...

Страница 17: ...imit of the inverter In this case the output voltage will quickly decrease to limit the output current of the inverter If the over current limit is continuously exceeded the inverter will shut down for 30 seconds and then automatically restart After three restarts followed by overload within 30 seconds of restarting the inverter will shut down and remain off To restart normal operation disconnect ...

Страница 18: ... down and restart levels They can be changed with VictronConnect computer or app Alternatively Dynamic Cut off can be implemented see https www victronenergy com live ve direct phoenix inverters dynamic cutoff 5 2 3 High battery voltage Reduce DC input voltage and or check for a faulty battery or solar charger in the system After shutting down due to a high battery voltage the unit will first wait...

Страница 19: ...ense connector is connected in reverse polarity to the BAT or BAT terminals 6 1 5 Error 8 Remote battery voltage sense failure connection lost Check if the V sense connector is properly connected to the battery terminals 6 1 6 Error 11 Battery high ripple voltage High DC ripple is usually caused by loose DC cable connections and or too thin DC wiring After the inverter has switched off due to high...

Страница 20: ...oltage cannot be reduced any further Consider modifying PV panel wiring to reduce the PV voltage 6 1 14 Error 43 Inverter shutdown Ground Fault The voltage difference between Neutral and Ground is too high Inverter or Multi not connected to the grid The internal ground relay is activated but the voltage over the relay is too high The relay might be damaged Multi connected to the grid The ground wi...

Страница 21: ...o standalone mode Our Chargers and Solarchargers automatically configure themselves to be BMS controlled when they are connected to one either direct or via a GX Device And that setting is semi permanent power cycling the charger will not reset it Here is what needs to be done to make the charger operate in stand alone mode again ie not controlled by a BMS VE Can solar chargers go into the setup m...

Страница 22: ...e the charger Please report this to your Victron dealer and ask them to escalate the matter to Victron as this error should never happen Preferably include firmware version and any other specifics VRM URL VictronConnect screenshots or similar 6 1 27 Error 121 Tester fail If the unit does not work and error 121 pops up as the active error the unit is faulty contact your dealer for a replacement If ...

Страница 23: ...roper or unreasonable use or misuse neglect exposure to excess moisture fire improper packing lightning power surges or other acts of nature This limited warranty does not cover damage deterioration or malfunction resulting from repairs attempted by anyone unauthorized by Victron Energy to make such repairs Non compliance with the instructions in this manual will render the warranty void Victron E...

Страница 24: ... V adjustable Earth leakage trip level 30 mA CHARGER Programmable charger voltage range 2 Minimum 36 V Maximum 62 V Charge voltage absorption default 57 6 V Charge voltage float default 55 2 V Maximum charge current 4 100 A Maximum DC charging power 4000 W Battery temperature sensor Included Battery voltage sense Yes GENERAL Parallel and 3 phase operation No Auxiliary output No Programmable relay ...

Страница 25: ...1 Can be adjusted to 60 Hz 5 Programmable relay which can be set for general alarm DC under voltage or genset start stop function including minimum closed time and relay off delay DC rating 4A up to 35VDC and 1A up to 70VDC 6 Protection key a output short circuit b overload c battery voltage too high d battery voltage too low e temperature too high f 230 VAC on inverter output g Solar earth leakag...

Страница 26: ...9 Appendix 9 1 Appendix A Connection Overview Figure 2 Inverter RS Smart Front Figure 3 Inverter RS Smart Bottom Inverter RS Smart Page 23 Appendix ...

Страница 27: ...Figure 4 User I O Inverter RS Smart Page 24 Appendix ...

Страница 28: ... 1 positive connection 4 AUX_IN2 Programmable auxiliary input 2 positive connection 5 REMOTE_L Remote on off connector Low 6 REMOTE_H Remote on off connector High 7 RELAY_NC Programmable relay Normally Closed connection 8 RELAY_COM Programmable relay common negative 9 TSENSE Temperature Sensor negative 10 TSENSE Temperature Sensor positive 11 VSENSE Voltage Sensor negative 12 VENSE Voltage Sensor ...

Страница 29: ...119 2 127 43 4 6 4x 350 240 380 26 3 4 1 98 3 120 120 55 30 6 2 3x Rev00 Dimension Drawing Inverter RS PIN482600000 Inverter RS 48 6000 230V Smart Dimensions in mm D E F C 1 2 3 4 B A 3 2 1 5 C D 4 6 7 8 A B 8 7 6 5 F E Inverter RS Smart Page 26 Appendix ...