12

 

5.5 Configuration with DIP switches 

 
Some settings can be changed with DIP switches 
 
Procedure: 
a) Turn the Compact on, preferably without load. 
b) Set the dipswitches as required. 
c) Store the settings by moving Dip switch 8 to “on” and back to “off”. 

 

5.5.1. DIP switch 1 and 2 

ds1 (default setting “off”). 
If no panel connected: should be “off”. 
When connecting a Control panel: should be “on”. 
 
ds2: (default setting “on”). 
If no panel connected: should be “on”. 
When connecting a Control panel: should be “off”. 
 

ds5: Inverter frequency 

 

 

off = 50Hz 

on = 60Hz  

 

ds6: Search Mode   

 

off = off   

on = on 

 

5.5.2 Exemplary settings  

Example 1 is the factory setting (since factory settings are entered by computer, all DIP 
switches of a new product are set to ‘off’, except for DS-2). 
 

 

DS-1 Panel option 

off   

DS-2 Panel option 

 

on 

DS-3 Not used 

 

 

DS-4 Not used 

 

 

DS-5 Frequency  

 

 

DS-6 Search mode 

off   

DS-7 Not used 

 

 

DS-8 Store setting 

 

 

 

DS-1 

off   

DS-2 

 

on 

DS-3 

 

 

DS-4 

 

 

DS-5 

off   

DS-6 

off   

DS-7 

 

 

DS-8 

 

 

 

DS-1 

 

on 

DS-2 

off   

DS-3 

 

 

DS-4 

 

 

DS-5 

 

on 

DS-6 

 

on 

DS-7 

 

 

DS-8 

 

 

 

Example 1: (factory setting) 

No panel connected 

No panel connected 

Frequency: 50Hz  

Search mode off 

8 store setting: off

 on

 off 

 
Example 2 

No panel connected

 

No panel connected 

Frequency: 50Hz  

Search mode off 

8 store setting: off

 on

 off 

 
Example 3 

Panel connected

 

Panel connected 

Frequency: 60Hz  

Search mode on 

8 store setting: off

 on

 off 

 
Store the settings (DS3-DS7) by changing switch ds-8 from off to on, and then back to off. 
The LED’s ‘Inverter’ and ‘eco mode’ and ‘alarm’ will flash four times to indicate acceptance of 
the settings. 

Содержание Phoenix Inverter 24/3000

Страница 1: ...os usar el inversor cargador MultiPlus en vez de este El conmutador está incluido es este producto y la función de cargador del MultiPlus puede deshabilitarse Los ordenadores y demás equipos electrónicos continuarán funcionando sin interrupción ya que el MultiPlus dispone de un tiempo de conmutación muy corto menos de 20 milisegundos Interfaz para el ordenador Todos los modelos disponen de un Puer...

Страница 2: ...Capacidad nominal CA 230V 4A Capacidad nominal CC 4 A hasta 35VDC 1 A hasta 60VDC 4 Protección a Cortocircuito de salida b Sobrecarga c Tensión de la batería demasiado alta d Tensión de la batería demasiado baja e Temperatura demasiado alta f 230 V CA en la salida del inversor g Ondulación de la tensión de entrada demasiado alta Phoenix Inverter Control This panel can also be used on a MultiPlus i...

Страница 3: ... Battery H UTP Cable Remote control J AC OUT G K Battery Link 1x 2x12V 1 100mm 100mm 100mm B A A D C D 3 1 2 10 3 5 8 4 6 7 9 Not included Included M F E T sense V sense G I MAIN MAIN TRICKLE H DIGITAL MULTI CONTROL I H L L N GND L N GND AC OUT 1 AC OUT 2 L N L N GND AC IN 1 AC IN 2 F TR charge G V sense E T sense N K J N O O 24V 48V F MAIN E J I AC OUT L N GND H G ...

Страница 4: ...Manual EN Handleiding NL Manuale FR Anleitung DE Manual ES Appendix Phoenix Inverter Compact 12 1200 230V 24 1200 230V 12 1600 230V 24 1600 230V ...

Страница 5: ......

Страница 6: ...Y PRODUCTS AND MAKES SUCH VICTRON ENERGY PRODUCTS AVAILABLE SOLELY ON AN AS IS BASIS IN NO EVENT SHALL VICTRON ENERGY B V BE LIABLE TO ANYONE FOR SPECIAL COLLATERAL INCIDENTAL OR CONSEQUENTIAL DAMAGES IN CONNECTION WITH OR ARISING OUT OF PURCHASE OR USE OF THESE VICTRON ENERGY PRODUCTS THE SOLE AND EXCLUSIVE LIABILITY TO VICTRON ENERGY B V REGARDLESS OF THE FORM OF ACTION SHALL NOT EXCEED THE PURC...

Страница 7: ......

Страница 8: ...in conjunction with the battery Always comply with the battery manufacturer s safety instructions WARNING Do not lift heavy loads without assistance Installation Read the installation instructions in the installation manual before installing the equipment This is a Safety Class I product supplied with a protective grounding terminal The chassis must be grounded A grounding point is located on the ...

Страница 9: ...product No liability can be accepted for any transport damage if the equipment is shipped in non original packaging Store the product in a dry environment the storage temperature must be between 20 C and 60 C Consult the battery manufacturer s manual in respect of transport storage charging recharging and disposal of the battery ...

Страница 10: ...er the load to another AC source the automatic transfer switch If an automatic transfer switch is required we recommend to using the MultiPlus or Quattro instead The switch is included in these products and the charger function of the MultiPlus Quattro can be disabled Computers and other electronic equipment will continue to operate without disruption because the MultiPlus Quattro features a very ...

Страница 11: ... switched on and supplies power to the load Battery operation inverter on eco mode off alarm eco The inverter is switched on and supplies power to the load Pre alarm overload or battery voltage low or inverter temperature high inverter on eco mode off alarm eco The inverter is switched off Alarm overload or battery voltage low or inverter temperature hig or DC ripple voltage on battery terminal wa...

Страница 12: ...nting see appendix A The appliance can be mounted horizontally as well as vertically vertical mounting is preferable The vertical position offers optimum cooling Try and keep the distance between the product and the battery to a minimum in order to minimize cable voltage losses For safety purposes this product should be installed in a heat resistant environment if it is used with equipment where a...

Страница 13: ... resistance is the important factor when working with low capacity batteries Please consult your supplier or the relevant sections of our book electricity on board downloadable from our website Procedure Proceed as follows to connect the battery cables Use an insulated box spanner in order to avoid shorting the battery Avoid shorting the battery cables Connect the battery cables the red and the bl...

Страница 14: ...ight N neutral earth and L1 phase Use a three wire cable with a flexible core and a cross section of 1 5 or 2 5 mm 4 4 Optional Connections A number of optional connections are possible 4 4 1 Remote on off switch remote Control panel The product can be remotely controlled in two ways With an external switch connection terminal H see appendix A Operates only if the switch on the Inverter is set to ...

Страница 15: ...oint must at least equal the sum of the required cross sections of the connections between the distribution point and the inverters Place the inverters close to each other but allow at least 10 cm for ventilation purposes under above and beside the units UTP cables must be connected directly from one unit to the other and to the remote panel Connection splitter boxes are not permitted Only one rem...

Страница 16: ...r frequency Output frequency Adjustability 50Hz 60Hz Inverter voltage Adjustability 210 245V Stand alone parallel operation 2 3 phase setting Using several devices it is possible to Increase total inverter power several devices in parallel Create a split phase system Create a 3 phase system The standard product settings are for standalone operation For parallel three phase or split phase operation...

Страница 17: ...t down 40 Watt linear load Turn on 100 Watt linear load AES Automatic Economy Switch Instead of the search mode the AES mode can also be chosen with help of VEConfigure only If this setting is turned on the power consumption in no load operation and with low loads is decreased by approx 20 by slightly narrowing the sinusoidal voltage Not adjustable with DIP switches Applicable in stand alone confi...

Страница 18: ...connection to the computer a RJ45 UTP cable and the MK2 2b RS485 to RS232 interface is required If the computer has no RS232 connection but does have USB a RS232 to USB interface cable is needed Both are available from Victron Energy 5 3 2 VE Bus System Configurator and dongle For configuring advanced applications and or systems with four or more inverters VE Bus System Configurator software must ...

Страница 19: ...all DIP switches of a new product are set to off except for DS 2 DS 1 Panel option off DS 2 Panel option on DS 3 Not used DS 4 Not used DS 5 Frequency DS 6 Search mode off DS 7 Not used DS 8 Store setting DS 1 off DS 2 on DS 3 DS 4 DS 5 off DS 6 off DS 7 DS 8 DS 1 on DS 2 off DS 3 DS 4 DS 5 on DS 6 on DS 7 DS 8 Example 1 factory setting 1 No panel connected 2 No panel connected 5 Frequency 50Hz 6 ...

Страница 20: ...shes Pre alarm alt 1 The DC input voltage is low Charge the battery or check the battery connections The alarm LED flashes Pre alarm alt 2 The ambient temperature is too high Place the inverter in a cool and well ventilated room or reduce the load The alarm LED flashes Pre alarm alt 3 The load on the inverter is higher than the nominal load Reduce the load The alarm LED flashes Pre alarm alt 4 Vol...

Отзывы: