Step 2: Exemplary settings
Example 1 is the factory setting (since factory settings are entered by computer, all DIP switches of a new product are set to ‘off’ and do
not reflect the actual settings in the microprocessor.).
DS-8 Ch. voltage
off
DS-7 Ch. voltage
on
DS-6 Absorpt. time
on
DS-5 Adaptive ch.
on
DS-4 Dyn. Curr. limit
off
DS-3 UPS function:
on
DS-2 Voltage
on
DS-1 Frequency
on
DS-8
off
DS-7
off
DS-6
on
DS-5
on
DS-4
off
DS-3
off
DS-2
on
DS-1
on
DS-8
on
DS-7
off
DS-6
on
DS-5
on
DS-4
on
DS-3
off
DS-2
off
DS-1
on
DS-8
on
DS-7
on
DS-6
off
DS-5
off
DS-4
off
DS-3
on
DS-2
off
DS-1
off
Step 2
Example 1 (factory setting):
8, 7 GEL 14,4V
6 Absorption time: 8 hours
5 Adaptive charging: on
4 Dynamic current limit: off
3 UPS function: on
2 Voltage: 120V
1 Frequency: 50Hz
Step 2
Example 2:
8, 7 OPzV 14,1V
6 Abs. time: 8 h
5 Adaptive ch.: on
4 Dyn. Curr. limit: off
3 UPS function: off
2 Voltage: 120V
1 Frequency: 50Hz
Step 2
Example 3:
8, 7 AGM 14,7V
6 Abs. time: 8 h
5 Adaptive ch: on
4 Dyn. Curr. limit: on
3 UPS function: off
2 Voltage: 120V
1 Frequency: 50Hz
Step 2
Example 4:
8, 7 Tub.-plate 15V
6 Abs. time: 4 h
5 Fixed abs. time
4 Dyn. Curr. limit: off
3 UPS function: on
2 Voltage: 120V
1 Frequency: 60Hz
To store the settings after the required values have been set: press the 'Down' button for 2 seconds (
lower
button to the right of the DIP
switches).
The temperature and low-battery LEDs will flash to indicate acceptance of the settings.
The DIP switches can be left in the selected positions, so that the ’other settings’ can always be recovered.