MultiPlus-II 48V 3kVA 120V
120/240 V AC-connection
Screw terminals 13 mm² (6 AWG)
Weight
19 kg
Dimensions (hxwxd) mm
536 x 275 x 147
STANDARDS
Safety
EN-IEC 60335-1, EN-IEC 60335-2-29
Emission, Immunity
EN 55014-1, EN 55014-2
EN-IEC 61000-3-2, EN-IEC 61000-3-3
IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6-3
1. Can be adjusted to 50 Hz
2. Protection key:
a. output short circuit
b. overload
c. battery voltage too high
d. battery voltage too low
e. temperature too high
f.
120 VAC on inverter output
g. input voltage ripple too high
3. Non-linear load, crest factor 3:1
4. At 25°C ambient
5. Programmable relay which can be set for general
alarm, DC under voltage or genset start/stop function.
AC rating: 120V / 4A, DC rating: 4A up to 35VDC and
1A up to 60VDC
MultiPlus-II 48V 3kVA 120V
Page 26
Technical Specifications