background image

7

Label

Name

Refrigerator Setting 

Factory Preset

Freezer Setting 

Factory Preset

Unit

Minimum

Maximum

            

 

Digital Inputs Parameters (continued)

i4

Memo door alarm in HACCP

Yes

Yes

-

No

Yes

This parameter is used to set the type of defrost interval. If real time defrost interval is required, set this to: (4) Calendar. The Hd parameters must be set 
to the time defrosts are required.

i10

Time to activate ENERGY SAVING mode 
by door input

240

240

min

0

999

The parameter is used to set the time length of door inactivity required to initiate the ENERGY SAVING mode. If set to zero, ENERGY SAVING mode will 
never activate because of door inactivity.

i13

Number of door openings to start safety 
defrost

120

120

-

0

240

This parameter is used to set the number of door openings required to initiate a safety defrost. If the normal defrost happens before this number of door 
openings has accumulated, the counter will be reset back to zero.

i14

Time of door opening to start safety 
defrost.

20

20

min

0

240

This parameter is used to initiate a defrost if the door has been open continuously for this amount of time.

             

Outputs Configuration Parameters

u9

Buzzer enabling

Enabled

Enabled

-

Disabled

Enabled

This parameter is used to enable or disable the alarm buzzer. The factory preset is for the buzzer to be active.

             

ENERGY SAVING Mode Configuration Parameters

HE1

ENERGY SAVING mode starting time.

0:00

0:00

-

0:00

23:59

This parameter is used if the user wants to set a time of day the ENERGY SAVING mode activates. See also "HE2".

HE2

ENERGY SAVING mode duration.

0'

0'

-

0'

23h59'

This parameter is used to set the duration of the ENERGY SAVING mode. See also "HE1".

             

Time Bands of Defrost (*optional feature for end-user to program scheduled defrost time periods)

Hd1

Defrost 1 starting time

---

---

-

0:00

---

Hd2

Defrost 2 starting time

---

---

-

0:00

---

Hd3

Defrost 3 starting time

---

---

-

0:00

---

Hd4

Defrost 4 starting time

---

---

-

0:00

---

Hd5

Defrost 5 starting time

---

---

-

0:00

---

Hd6

Defrost 6 starting time

---

---

-

0:00

---

*Note: 

These parameters are used to set real time defrosts. Up to 6 defrost times can be programmed. See also "d8" on page 6.

USER PARAMETERS (continued)

*Refer to the "PARAMETER ACCESS & ADJUSTMENT" section on page 5.

Содержание 50707412

Страница 1: ...ng Manual 110 Wo o d crest Roa d C he rry H ill N J 0 8003 Phone 856 428 4200 Fax 856 673 0038 Website www victoryrefrigeration com E Mail parts victoryrefrigeration com order entry victoryrefrigerati...

Страница 2: ...RTANT INFORMATION PLEASE READ Please read these instructions carefully before installing or using If recommended procedures are not followed warranty claims may be denied Your Warranty Registration in...

Страница 3: ...d bill from the servicing agency must accompany the claim together with full details of the service problems diagnosis and work performed Victory will determine at its sole discretion whether further...

Страница 4: ...ning through a filter dryer first to remove any dirt or foreign particles D Defrost The term is used to identify the function of a refrigerator or freezer to remove frost or ice from the internal evap...

Страница 5: ...rs 6 7 PERIODIC CLEANING Cabinet Cleaning 8 Condenser Maintenance 8 Lubrication 9 Installing Replacement Door Gasket 9 TROUBLESHOOTING GUIDE FOR COMMON PROBLEMS Common Problems Remedies 10 COMMON REPL...

Страница 6: ...ion as possible before removing skid 4 Remove the shipping skid by tipping the cabinet forward Remove the shipping bolts with 3 4 box wrench while the cabinet is held in one direction Repeat this proc...

Страница 7: ...a dedicated circuit with separate grounding wire is required Controller When first supplying power to the cabinet there will be approximately a one minute delay before the compressor and fan motors s...

Страница 8: ...ation KEYPAD BUTTONS Note Use V TEMP Keypad illustration above to follow these instructions Button 1 ON STANDBY Press this button for a few seconds to switch the cabinet on and off Button 2 MANUAL DEF...

Страница 9: ...This requires the user to press a button to clear the alarm The HACCP LED provides information regarding the memory status of the HACCP alarms If it is on not all of the information regarding the HAC...

Страница 10: ...when the defrost terminates on time rather than temperature a Verify that the evaporator probe is intact and in the evaporator coil b Press any button to restore normal display The unit will continue...

Страница 11: ...erval is required set this to 4 Calendar The Hd parameters must be set to the time defrosts are required d20 Max Time for Safety Defrost in Normal Operation N A 120 0 500 This parameter is used to set...

Страница 12: ...rost 20 20 min 0 240 This parameter is used to initiate a defrost if the door has been open continuously for this amount of time Outputs Configuration Parameters u9 Buzzer enabling Enabled Enabled Dis...

Страница 13: ...temperature Condenser Maintenance To keep your cabinet running efficiently it is recommended that you clean the condenser coil once every three months or immediately after the COH LED displays and ala...

Страница 14: ...ed Removing Beginning at one corner pry the gasket loose from the retaining strip Peel remainder of the gasket from the door and discard Replacing Before replacing be sure the gasket and door are at r...

Страница 15: ...ture Poor air circulation in cabinet Re arrange product to allow proper air circulation Excessive amount of warm product loaded in cabinet Allow adequate time for product to cool down Prolonged door o...

Страница 16: ...inet Narrow Extra Wide 50617203 Evaporator Coil 86E10 1 Section Freezer 1 per cabinet Narrow Extra Wide 50616902 Evaporator Coil 86E21 2 3 Section Freezer 1 per cabinet Narrow Extra Wide 50639401 Evap...

Страница 17: ...r Half Lower Left Hinged with S S Liner 1 per refrigerator freezer half section 10848813 Door Extra Wide Half Upper Right Hinged with S S Liner 1 per EW 1 2 section half door refrig frzr 10848814 Door...

Страница 18: ...13 WIRING DIAGRAMS WIRING DIAGRAMS 1 2 3 Section Refrigerator Wiring Diagram for 115 Volt 15 Amp 20 Amp 1 2 3 Section Refrigerator Wiring Diagram for 115 Volt 208 230 Volt Condensing Unit...

Страница 19: ...14 1 2 3 Section Freezer Wiring Diagram for 115 Volt 15 Amp 20 Amp 1 2 3 Section Freezer Wiring Diagram for 115 Volt 208 230 Volt Condensing Unit...

Страница 20: ...t Roa d C he rry H ill N J 0 8003 Phone 856 428 4200 Fax 856 673 0038 Website www victoryrefrigeration com E Mail parts victoryrefrigeration com order entry victoryrefrigeration com service victoryref...

Отзывы: