7
Label
Name
Refrigerator Setting
Factory Preset
Freezer Setting
Factory Preset
Unit
Minimum
Maximum
Digital Inputs Parameters (continued)
i4
Memo door alarm in HACCP
Yes
Yes
-
No
Yes
This parameter is used to set the type of defrost interval. If real time defrost interval is required, set this to: (4) Calendar. The Hd parameters must be set
to the time defrosts are required.
i10
Time to activate ENERGY SAVING mode
by door input
240
240
min
0
999
The parameter is used to set the time length of door inactivity required to initiate the ENERGY SAVING mode. If set to zero, ENERGY SAVING mode will
never activate because of door inactivity.
i13
Number of door openings to start safety
defrost
120
120
-
0
240
This parameter is used to set the number of door openings required to initiate a safety defrost. If the normal defrost happens before this number of door
openings has accumulated, the counter will be reset back to zero.
i14
Time of door opening to start safety
defrost.
20
20
min
0
240
This parameter is used to initiate a defrost if the door has been open continuously for this amount of time.
Outputs Configuration Parameters
u9
Buzzer enabling
Enabled
Enabled
-
Disabled
Enabled
This parameter is used to enable or disable the alarm buzzer. The factory preset is for the buzzer to be active.
ENERGY SAVING Mode Configuration Parameters
HE1
ENERGY SAVING mode starting time.
0:00
0:00
-
0:00
23:59
This parameter is used if the user wants to set a time of day the ENERGY SAVING mode activates. See also "HE2".
HE2
ENERGY SAVING mode duration.
0'
0'
-
0'
23h59'
This parameter is used to set the duration of the ENERGY SAVING mode. See also "HE1".
Time Bands of Defrost (*optional feature for end-user to program scheduled defrost time periods)
Hd1
Defrost 1 starting time
---
---
-
0:00
---
Hd2
Defrost 2 starting time
---
---
-
0:00
---
Hd3
Defrost 3 starting time
---
---
-
0:00
---
Hd4
Defrost 4 starting time
---
---
-
0:00
---
Hd5
Defrost 5 starting time
---
---
-
0:00
---
Hd6
Defrost 6 starting time
---
---
-
0:00
---
*Note:
These parameters are used to set real time defrosts. Up to 6 defrost times can be programmed. See also "d8" on page 6.
USER PARAMETERS (continued)
*Refer to the "PARAMETER ACCESS & ADJUSTMENT" section on page 5.