                                                IOM – VL71 FLOODLIGHT

VL71 IOM IECEx ATEX 

 

 

Issue 02      May 08 

 

 

 

 

1

 

 

 

 

Issue 02

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS 

Victor: VL71 FLOODLIGHT (IECEx)  (ATEX) 

Important :

     Please read these instructions carefully before installing or maintaining this equipment. 

Good electrical practices should be followed at all times and this data should be used 
As a guide only. 

                                       

                                                                      

Содержание VL71

Страница 1: ...ION OPERATION AND MAINTENANCE INSTRUCTIONS Victor VL71 FLOODLIGHT IECEx ATEX Important Please read these instructions carefully before installing or maintaining this equipment Good electrical practices should be followed at all times and this data should be used As a guide only ...

Страница 2: ...er 1 0 Introduction VL71 nR FLOODLIGHT The VL71 Floodlight is designed for all round lighting applications It is suitable for use with tubular discharge lamps and single ended tungsten halogen lamps A gear box is used with the low voltage range of 400w HID versions The floodlight is restricted in its mounting position The beam of the floodlight may be aimed at any angle but the control gear must a...

Страница 3: ... where the dust could lie on the glass The temperature on the glass is the hottest point on the luminaire and any obstruction of the radiation from the luminaire would cause the surface temperature to increase 3 2 Tools A cross head screwdriver blade to open hinged cover 3mm and 5mm flat blade screwdriver Suitable spanners for installing cable glands Pliers knife wire strippers cutters 3 3 Electri...

Страница 4: ...mply with the certification for installation and use within the EU cable glands and sealing plugs must have ATEX component approval For installation outside the EU suitable cable glands in accordance with IECEx EN 60079 0 will meet the technical requirements The cable and gland assembly when installed must maintain the IP66 67 rating of the floodlight The cable gland must withstand an impact value...

Страница 5: ... should be opened up dried out and any likely ingress points eliminated by re gasketting re greasing or other replacement 3 Check the cable gland for tightness and tighten if necessary 4 Check any external earthing 5 Examine the glass for any signs of damage Clean glass 6 When relamping check that the cover gasket has not softened or become excessively deformed if in doubt replace see section 4 0 ...

Страница 6: ...er judgement of what is required Use MCB s suitable for inrush currents to reduce ratings The normal capacitor current will probably be the determining factor 0 076A per μF at 240V 50Hz adjust for other volts by multiplication x 6 5 for 60Hz For HBC fuses use 1 5 x normal capacitor current For GLS inrush use 6 x rated current All calculations must satisfy wiring regulations Note Starting and runni...

Страница 7: ... SON T 150 T4 55 70 15 400 T3 55 80 25 250 T4 55 70 15 MBI T 150 110 120V 50 60Hz T4 55 50ºC 70 15 Table 1 Starting and Running Currents Refer to section 4 0 LAMP Lamp A Start A Run A Capacitance μF Circuit Power W 150W SON T 1 8 1 45 0 8 20 175 250W SON T 3 0 2 35 1 3 30 285 400W SON T 4 6 4 0 2 2 40 445 150W MBI 1 8 1 6 0 8 20 175 250W MBI 3 0 2 7 1 35 30 285 400W MBI 4 2 4 0 2 2 40 445 Notes Mi...

Страница 8: ...44 Fax 44 0 141 810 9642 Email info victor lighting com Web www victor lighting com For Technical support please contact technical victor lighting com Registered Office Mitre House 160 Aldersgate Street London EC1A 4DD Registered No 669157 Note Victor Lighting reserve the right to amend characteristics of our products and all data is for guidance only ...