                                             IOM – VL71 FLOODLIGHT

 

  

VL71 IOM

 IECEx 

ATEX    

Issue 02  

May 08   

 

 

2

0.0 Specification 

 

Type Of Protection   

Ex nR (restricted breathing enclosure), Ex  nA (non-sparking).  

 

Protection Standards 

(IEC) EN 60079-0, (IEC) EN 60079-15, (IEC) EN 61241-0, (IEC) EN 61241-1. 

ATEX Equipment 
Classification 

Group II Category 3 G 
Group II Category 3 D 

 

Area Classification 

Zone 2 areas to (IEC) EN 60079-10 and installation to (IEC) EN 60079-14 
Zone 22 areas to (IEC) EN 61241-10 and installation to (IEC) EN 61241-14. 

 

Certificate 

 

EC Type Examination Certificate Baseefa07ATEX0119X
IECEx  Certificate  IECEx BAS07.0025X 

 

Equipment Coding 

Ex nR II T3 
Ex tD A22 IP6*  T**ºC  (Refer to table 0) 
Ex nA II T3 
Ex tD A22 IP6* T**ºC 

 

Ingress Protection 

IP66 and IP67 to BS EN 60529 

 

CE Mark 

 

The CE marking of this product applies to "The Electrical Equipment (Safety) Regulations 1994", 
‘’The Electromagnetic Compatibility Regulations 1992", the “Waste Electrical and Electronic 
Equipment Regulations 2006” and the "Equipment and Protective Systems intended for use in 
Explosive Atmospheres Regulations 1996". [This legislation is the equivalent in UK law of EC 
directives 73/23EEC, 89/336/EEC, 2002/96/EC and 94/9/EC respectively]. 

 ATEX 

Declaration 

The Equipment is declared to meet the provisions of the ATEX directive (94/9/EC) by 
reason of the EC Type Examination and compliance with the Essential Health and 
Safety Requirements. 
I MacLeod    Technical Manager   

1.0    

Introduction – VL71  nR FLOODLIGHT.

The VL71 Floodlight is designed for all round lighting applications.  It is suitable for use with tubular discharge lamps and 
single ended tungsten halogen lamps. A gear box is used with the low voltage range of 400w HID versions.  
The floodlight is restricted in its mounting position. The beam of the floodlight may be aimed at any angle but the control gear
must always be mounted on or below the axis of rotation of the floodlight. 
The floodlight is designed to be safe in normal operation. 
The floodlight should not be used in conditions where there are environmental, vibration or shock conditions above the normal 
for fixed installations. 
The gaskets should not be exposed to hydrocarbons in liquid or high concentration vapour states. 
The floodlight is suitable for applications where category 3 apparatus is used. The application is for ignitable gas and dust 
atmospheres. The floodlight is not suitable for portable applications. 

Note : 

Lamp ranges and temperature ratings are outlined in TABLE 0. 

 

 

 

 

2.0     

Storage

Luminaires and control gear boxes are to be stored in cool dry conditions preventing ingress of moisture and condensation. 

3.0 Installation 

and 

Safety 

3.1     

General

There is no health hazards associated with this product whilst in normal use.  However, care should be exercised during the 
following operations.  Installation should be carried out in accordance with (IECEx) 

EN 60079-14

 or the local hazardous area 

code of practice, whichever is appropriate. 
In the UK the requirements of the 

'Health and Safety at Work Act'

 must be met. 

Содержание VL71

Страница 1: ...ION OPERATION AND MAINTENANCE INSTRUCTIONS Victor VL71 FLOODLIGHT IECEx ATEX Important Please read these instructions carefully before installing or maintaining this equipment Good electrical practices should be followed at all times and this data should be used As a guide only ...

Страница 2: ...er 1 0 Introduction VL71 nR FLOODLIGHT The VL71 Floodlight is designed for all round lighting applications It is suitable for use with tubular discharge lamps and single ended tungsten halogen lamps A gear box is used with the low voltage range of 400w HID versions The floodlight is restricted in its mounting position The beam of the floodlight may be aimed at any angle but the control gear must a...

Страница 3: ... where the dust could lie on the glass The temperature on the glass is the hottest point on the luminaire and any obstruction of the radiation from the luminaire would cause the surface temperature to increase 3 2 Tools A cross head screwdriver blade to open hinged cover 3mm and 5mm flat blade screwdriver Suitable spanners for installing cable glands Pliers knife wire strippers cutters 3 3 Electri...

Страница 4: ...mply with the certification for installation and use within the EU cable glands and sealing plugs must have ATEX component approval For installation outside the EU suitable cable glands in accordance with IECEx EN 60079 0 will meet the technical requirements The cable and gland assembly when installed must maintain the IP66 67 rating of the floodlight The cable gland must withstand an impact value...

Страница 5: ... should be opened up dried out and any likely ingress points eliminated by re gasketting re greasing or other replacement 3 Check the cable gland for tightness and tighten if necessary 4 Check any external earthing 5 Examine the glass for any signs of damage Clean glass 6 When relamping check that the cover gasket has not softened or become excessively deformed if in doubt replace see section 4 0 ...

Страница 6: ...er judgement of what is required Use MCB s suitable for inrush currents to reduce ratings The normal capacitor current will probably be the determining factor 0 076A per μF at 240V 50Hz adjust for other volts by multiplication x 6 5 for 60Hz For HBC fuses use 1 5 x normal capacitor current For GLS inrush use 6 x rated current All calculations must satisfy wiring regulations Note Starting and runni...

Страница 7: ... SON T 150 T4 55 70 15 400 T3 55 80 25 250 T4 55 70 15 MBI T 150 110 120V 50 60Hz T4 55 50ºC 70 15 Table 1 Starting and Running Currents Refer to section 4 0 LAMP Lamp A Start A Run A Capacitance μF Circuit Power W 150W SON T 1 8 1 45 0 8 20 175 250W SON T 3 0 2 35 1 3 30 285 400W SON T 4 6 4 0 2 2 40 445 150W MBI 1 8 1 6 0 8 20 175 250W MBI 3 0 2 7 1 35 30 285 400W MBI 4 2 4 0 2 2 40 445 Notes Mi...

Страница 8: ...44 Fax 44 0 141 810 9642 Email info victor lighting com Web www victor lighting com For Technical support please contact technical victor lighting com Registered Office Mitre House 160 Aldersgate Street London EC1A 4DD Registered No 669157 Note Victor Lighting reserve the right to amend characteristics of our products and all data is for guidance only ...

Отзывы: