I-769N.Deluge
/ Series 769N FireLock NXT
™
Deluge Valve
/ Installation, Maintenance, and Testing Manual
REQUIRED WATER FLOW ALARM TEST
Refer to NFPA 25, FM Datasheets, or any applicable local requirements
to perform water flow alarm tests. The authority having jurisdiction in
the area may require these inspections on a more frequent basis. Verify
these requirements by contacting the authority having jurisdiction in the
affected area.
1.
Notify the authority having jurisdiction, remote station alarm
monitors, and those in the affected area that the water flow alarm
test will be performed.
CAUTION
• Use caution to prevent opening the system main drain valve
accidentally.
• Opening the system main drain valve will cause the valve to
operate.
Failure to pipe the system main drain valve to a proper wastewater
drain will result in property damage.
2.
Open the water supply main drain valve fully to flush the water
supply of any contaminants.
3.
Close the water supply main drain valve.
4.
Open the alarm test ball valve. Confirm that mechanical and
electrical alarms are activated and that remote monitoring stations,
if provided, receive an alarm signal.
5.
Close the alarm test ball valve after verifying proper operation of all
alarms.
6.
Push in the ball drip plunger on the alarm manifold assembly to
verify that there is no pressure in the alarm line.
7.
Verify that all alarms stopped sounding, that the alarm line drained
properly, and that remote station alarms reset properly.
8.
Confirm that the ball drip on the alarm manifold assembly is not
leaking water or air.
9.
Notify the authority having jurisdiction, remote station alarm
monitors, and those in the affected area that the valve is back in
service. Provide test results to the authority having jurisdiction, if
required.
Water Supply
Main Drain
Valve
(Steps 2 & 3)
Ball Drip
Plunger
(Steps 6 & 8)
Alarm Test
Ball Valve
(Steps 4 & 5)
Pneumatic (Dry Pilot) Release Trim Shown
(Manual pull station not shown for clarity of components)
I-769N.Deluge_26
REV_F