background image

I-768N 

/ Series 768N FireLock NXT

 Dry Valve

 

/ Installation, Maintenance, and Testing Manual

AIR SUPPLY REQUIREMENTS

The required air pressure for Series 768N FireLock NXT Dry Valves is 13 psi/90 kPa/0.9 Bar minimum, regardless of the system supply water 
pressure. Normal air pressure should not exceed 20 psi/138 kPa/1.4 Bar. Failure to maintain air pressure within the 13 psi/90 kPa/0.9 Bar to 
18 psi/124 kPa/1.2 Bar range may delay system operation response time.
The Series 746-LPA Dry Accelerator must be used only on systems operating below 20 psi/138 kPa/1.4 Bar of air. If air pressure is higher than 
20 psi/138 kPa/1.4 Bar, the Series 746 Dry Accelerator should be used.

FOR VdS APPROVED VALVES ONLY:

 The minimum air pressure for Series 768N FireLock NXT Dry Valves installed with Series 746-LPA Dry 

Accelerators shall be 16 psi/110 kPa/1.1 Bar. The maximum air pressure shall be 19 psi/130 kPa/1.3 Bar.
If multiple Series 768N FireLock NXT Dry Valves are installed with a common air supply, isolate the systems with a spring-loaded, soft-seated ball 
check valve to ensure air integrity for each system. Good practice is to include a ball valve for isolation and service of each individual system.
The engineer/system designer is responsible for sizing the compressor so that the entire system is charged to the required air pressure within 
30 minutes. DO NOT oversize the compressor to provide more airflow. An oversized compressor will slow down or possibly prevent valve operation.
If the compressor fills the system too fast, it may be necessary to restrict the air supply. Restricting the air supply will ensure that air being exhausted 
from an open sprinkler or manual release valve is not replaced by the air supply system as fast as it is being exhausted.

BASE- OR RISER-MOUNTED AIR COMPRESSORS

For base- or riser-mounted air compressors, the recommended air pressure of 13 psi/90 kPa/0.9 Bar is the “on” or “low” pressure setting for the 
compressor. The “off” or “high” pressure setting should be 18 psi/124 kPa/1.2 Bar.
When a base- or riser-mounted air compressor supplies air to a Series 768N FireLock NXT Dry Valve, it is not necessary to install the Victaulic Series 
757 Regulated Air Maintenance Trim Assembly (AMTA). In this case, the air line of the compressor connects to the trim at the fitting where the Series 
757 Regulated AMTA is installed normally (refer to the applicable trim drawing). If the compressor is not equipped with a pressure switch, the Series 
757P Air Maintenance Trim Assembly with Pressure Switch should be installed.

NOTICE

•  Victaulic recommends a maximum of two Series 768N FireLock NXT Dry Valves per Series 757 Regulated AMTA or Series 757P AMTA with 

Pressure Switch.

SHOP AIR OR TANK-MOUNTED AIR COMPRESSORS

In the event a compressor becomes inoperative, a properly sized tank-mounted air compressor provides the greatest protection for systems.
When shop air or a tank-mounted air compressor is used, the Series 757 Regulated AMTA must be installed. The Series 757 Regulated AMTA 
provides proper air regulation from the air reservoir to the sprinkler system.
For tank-mounted air compressors, the recommended air pressure of 13 psi/90 kPa/0.9 Bar should be used as the set point for the air regulator. The 
“on” pressure of the compressor should be at least 5 psi/34 kPa/0.3 Bar above the set point of the air regulator.

COMPRESSOR REQUIREMENTS AND SETTINGS FOR A SERIES 768N FIRELOCK NXT DRY VALVE 

INSTALLED WITH A SERIES 746-LPA DRY ACCELERATOR

Set the air regulator of the Series 757 Regulated AMTA to a minimum of 13 psi/90 kPa/0.9 Bar.

FOR VdS APPROVED VALVES ONLY:

 The minimum air pressure for Series 768N FireLock NXT Dry Valves installed with Series 746-LPA Dry 

Accelerators shall be 16 psi/110 kPa/1.1 Bar. The maximum air pressure shall be 19 psi/130 kPa/1.3 Bar.

The Series 757P Air Maintenance Trim Assembly with Pressure Switch MUST NOT be used on a Series 768N FireLock NXT Dry Valve installed 
with a Series 746-LPA Dry Accelerator, unless a tank and air regulator are added.

In the event a compressor becomes inoperative, a properly sized tank-mounted air compressor provides the greatest protection for systems installed 
with a Series 746-LPA Dry Accelerator. In this situation, air can be supplied continuously to the sprinkler system for an extended time period. 

NOTE:

 The Series 757 Regulated AMTA should be used with a tank-mounted air compressor to supply air to a Series 768N FireLock NXT Dry Valve 

when the Series 746-LPA Dry Accelerator is used. The use of an air regulator with a base- or riser-mounted air  compressor could cause short cycling, 
resulting in premature wear of the  compressor.
The air regulator of the Series 757 Regulated AMTA is a relief-type design. Any pressure in the system that is above the set point of the air regulator 
will be released. Therefore, charging the air regulator above the set point could cause premature operation of a valve installed with a Series 746-LPA 
Dry Accelerator.

SETTINGS FOR AIR SUPERVISORY PRESSURE SWITCHES AND ALARM PRESSURE SWITCHES

1.

  Air supervisory pressure switches are required for dry systems and must be set according to the following notes. 

NOTE:

 Switches for VQR 

assemblies are pre-set at the factory.

 

1a.

  Wire the air supervisory pressure switches to activate a low-pressure alarm signal. 

NOTE:

 In addition, the local authority having jurisdiction  

 

may require a high-pressure alarm. Contact the local authority having jurisdiction for this requirement.

 

1b.

  Set the air supervisory pressure switches to activate at 2 – 4 psi/14 – 28 kPa/0.1 – 0.3 Bar below the minimum air pressure required (but  

 

not  lower  than  10 psi/69 kPa/0.7 Bar).

 

1c.

  Wire the alarm pressure switch to activate a water flow alarm.

 

1d.

  Set the alarm pressure switch to activate on a pressure rise of 4 – 8 psi/28 – 55 kPa/0.3 – 0.6 Bar.

I-768N_9

REV_C

Содержание 768N FireLock NXT Series

Страница 1: ...ore attempting to install remove adjust or perform maintenance on any Victaulic piping products Wear safety glasses hardhat and foot protection Save this installation maintenance and testing manual fo...

Страница 2: ...se the 1 4 turn vent ball valve Step 9b If a Series 746 LPA Dry Accelerator is installed open the isolation ball valve This will set the accelerator Step 10 Open the water supply main drain valve Step...

Страница 3: ...the water flow alarm test will be performed 2 Open the water supply main drain valve fully to flush the water supply of any contaminants 3 Close the water supply main drain valve 4 Open the alarm test...

Страница 4: ...failure resulting in death or serious personal injury and property damage 1 Read and understand all instructions and refer to the trim diagrams before installing maintaining or testing this Victaulic...

Страница 5: ...Vic Quick Riser VQR assembly is shown 1 Ensure that all components are included in the shipment and that all necessary tools are available for installation Verify that the provided trim drawing match...

Страница 6: ...ns inches mm Approx Weight Each lbs kg A A1 B C D D1 E F G H K Without Trim With Trim 1 9 00 16 37 32 75 9 25 16 50 11 00 9 25 3 25 10 25 22 50 6 00 16 7 43 0 228 60 415 80 832 235 419 279 235 83 260...

Страница 7: ...FireLock NXT Dry Valve 2 FireLock Rigid Coupling 3 Water Supply Main Control Valve 4 Drip Cup 5 Water Supply Main Drain Valve Flow Test 6 System Pressure Gauge Gauge Valve Assembly 7 System Main Drai...

Страница 8: ...ssembly Bolt 8 Clapper Spring 9 Clapper Shaft 10 Clapper Shaft Bushing and O Ring Qty 2 Item Description 11 Cover Plate 12 Cover Plate Gasket 13 Cover Plate Bolts 14 Latch 15 Latch Spring 16 Latch Spr...

Страница 9: ...unted air compressor provides the greatest protection for systems When shop air or a tank mounted air compressor is used the Series 757 Regulated AMTA must be installed The Series 757 Regulated AMTA p...

Страница 10: ...I 768N Series 768N FireLock NXT Dry Valve Installation Maintenance and Testing Manual SECTION I Initial System Setup I 768N_10 REV_C...

Страница 11: ...st ball valve is closed Step 4 Charge the system with air by turning on the compressor or by opening the fast fill ball valve on the AMTA Charge the system to 13psi 90kPa 0 9Bar minimum Refer to the A...

Страница 12: ...ater to flow through the auto drain tube Step 9 Verify that the charge line pressure is equal to the supply pressure and verify that the auto drain is set by pulling up on the auto drain sleeve Step 9...

Страница 13: ...jurisdiction remote station alarm monitors and those in the affected area that the system is in service Valve Normal Operating Position Water Supply Main Control Valve Open Water Supply Main Drain Va...

Страница 14: ...I 768N Series 768N FireLock NXT Dry Valve Installation Maintenance and Testing Manual SECTION II Resetting the System I 768N_14 REV_C...

Страница 15: ...main drain valve Confirm that the system is drained Step 3a Push in the ball drip plunger to release pressure Step 4 Close the system main drain valve Step 5 Confirm that all system drains are shut an...

Страница 16: ...accordance with current NFPA 25 requirements or in accordance with the requirements of the local authority having jurisdiction whichever is more stringent Always refer to the instructions in this man...

Страница 17: ...echanical damage and corrosion Replace any damaged or corroded parts 4 Confirm that the dry valve and trim are located in an area that is not subject to freezing temperatures 5 Confirm that all valves...

Страница 18: ...quirements The frequency of inspections must be increased in the presence of contaminated water supplies corrosive scaling water supplies and corrosive atmospheres Any activities that require taking t...

Страница 19: ...water supply main drain valve is fully open record the water supply pressure from the water supply gauge as the r esidual pressure 8 Close the water supply main drain valve slowly 9 Record the water p...

Страница 20: ...upply main drain valve fully to flush the water supply of any contaminants 3 Close the water supply main drain valve 4 Open the alarm test ball valve Confirm that mechanical and electrical alarms are...

Страница 21: ...ow air alarm activates 8 Close the system main drain valve 9 Close the slow fill ball valve on the AMTA if equipped 10 Open the fast fill ball valve on the AMTA Bring the pressure back up to the norma...

Страница 22: ...drain valve fully to flush the water supply of any contaminants 4 Close the water supply main control valve to the point where additional closure will not provide flow through the water supply main dr...

Страница 23: ...alve fully to flush the water supply of any contaminants 4 Close the water supply main drain valve 5 Open the remote system test valve inspector s test connection to simulate the operation of a sprink...

Страница 24: ...f the local authority having jurisdiction whichever is more stringent Always refer to the instructions in this manual for additional inspection and testing requirements The frequency of inspections mu...

Страница 25: ...e removed Failure to follow this instruction could result in death or serious personal injury and property damage 11 After all pressure is released from the system loosen the cover plate bolts slowly...

Страница 26: ...ntaining the fire protection system in proper operating condition To ensure proper system operation valves must be inspected in accordance with current NFPA 25 requirements or in accordance with the r...

Страница 27: ...ION Use only Victaulic supplied replacement parts Failure to follow this instruction could cause improper valve operation resulting in property damage 6 Pry the clapper seal along with the seal ring o...

Страница 28: ...Y BOLT BOLT SEAL TORQUES Nominal Size inches or mm Required Torque inch lbs N m 1 1 2 40 5 2 40 5 2 1 2 90 10 76 1mm 90 10 3 90 10 4 110 12 165 1mm 160 18 6 160 18 8 160 18 12 Replace the cover plate...

Страница 29: ...haft bushings into the valve body until hand tight 9b Tighten the clapper shaft bushings until metal to metal contact occurs with the valve body DO NOT exceed 10 ft lbs 14 N m of torque on the clapper...

Страница 30: ...2 1 2 60 81 76 1mm 60 81 3 60 81 4 100 136 165 1mm 115 156 6 115 156 8 100 136 6 Place the system back in service by following the Resetting the System section REMOVING AND REPLACING THE DIAPHRAGM 1...

Страница 31: ...e Required Internal Inspection section 2 Remove the existing cartridge from the air manifold and priming manifold assemblies shown above Rinse the cartridges to remove any deposits 3 Install the corre...

Страница 32: ...I 768N Series 768N FireLock NXT Dry Valve Installation Maintenance and Testing Manual SECTION VII Troubleshooting I 768N_32 REV_C...

Страница 33: ...ricting airflow When the AutoVent Sleeve of the Series 776 Low Pressure Actuator is pulled up the screw does not stay set in the UP position The Series 776 Low Pressure Actuator is not receiving enoug...

Страница 34: ...it und ohne Schnell ffner S 746 LPA Approval no G4070037 Name of product NXT S 768 DN 100 mit und ohne Schnell ffner S 746 LPA Approval no G4070038 Name of product NXT S 768 DN 150 mit und ohne Schnel...

Отзывы: