If the unit is operated unmounted, insert a #6 or metric screw through each hole

from below and secure with a nut on top, torqued to 6 in-lbs (0.7 N-m).

Output Terminal Connections. A hardware kit with parts for output terminal

connections is provided with each FlatPAC unit. The following drawing shows the

assembly of those parts for the proper connection of metal power terminals.

Assembly for PCB power terminals is the same except that they do not require an

external tooth lockwasher. Consult the table below for the recommended torque

level for each stud size.

For More Information

The Vicor Applications Manual and product data sheet contain complete

information about FlatPAC AC-DC Switchers. To receive literature or to consult

an applications engineer about installation or operation of this product, contact

your nearest Vicor office. (See page 8.)

(Bitte lesen Sie die Sicherheits-Vorschriften auf Seite 8.)

“AMP” and “Faston” are registered trademarks of AMP, Incorporated, Harrisburg, PA.

7

Metal Terminal

Drawing:  P.N. 10894 #1

Terminal and

Terminal

Recommended

Product Model

Style

Stud Size

Torque

–Output, +Output

LF-, PA/PF-, &

PCB

8-32 UNC

10 in-lbs (1.1 N-m)

RA/RF-Series

MA/MF- &

Metal

10-32 UNC

15 in-lbs (1.7 N-m)

NA/NF-Series

QA/QF-Series

PCB

8-32 UNC

10 in-lbs (1.1 N-m)

Metal

10-32 UNC

15 in-lbs (1.7 N-m)

Supervisory

Sized to accept AMP Faston

®

insulated 

All models

receptacle #2-520184-2

EXTERNAL TOOTH

LOCKWASHER

#10 TERMINAL

RETAINING NUT

#10 NUT PLATE

USER OUTPUT

TERMINALS

#10 BRASS STUD

HELICAL

LOCKWASHER

(FITS WITHIN

OPENING PROVIDED)

TERMINAL COVER

NEGATIVE

Содержание AC-DC

Страница 1: ...up and three up models maximum output 400 W and 600 W feature an autoranging input which automatically senses the input line voltage and sets the power supply s input range accordingly FlatPAC s unique modular design accommodates over 10 000 different configurations FlatPAC switchers that contain BatMod current source modules instead of VI 200 converters are indicated by the suffix BM following th...

Страница 2: ...Vce sat 0 4 V 1 5 mA Maximum voltage is 70 Vdc 30 mA max Disable MOD DIS MOD DIS V AC OK AC OK BUS OK BUS OK Status 1 5mA max V r r AC Mains Connections Supervisory Connections 2 up and 3 up models AC Mains Earth Ground MOD DIS MOD DIS AC OK AC OK BUS OK BUS OK Internal Supervisory Circuits Optocouplers Autoranging models Do not connect Manual strap models Connect for 115 Vac Open for 230 Vac ST2 ...

Страница 3: ...VLINE 90 180 Vac AC Line Interrupted AC Line AC OK DC OK T0 T1 T2 T3 T4 Conditions Full Load 90 180 Vac AC Line Timing Diagram Status Signals 2 up and 3 up models Output Trimming All models with VI 200s Battery Charger External Control Functions OUT VTRIM ITRIM IMON OUT Programmable Current Source 12 48V Battery Load OR Typical Applications FlatPACs with BatMods only Time Interval Min Typ Max Unit...

Страница 4: ...odels 10 11 8 9 7 6 1 2 5 4 3 7 38 187 5 1 99 50 6 4 42 106 7 20 5 1 18 4 6 6 00 152 4 2 288 58 12 2 420 61 47 7 00 177 8 20 5 1 5 PLACES 25 6 4 5 PLACES 19 4 8 12 ø 150 005 ø3 81 0 13 THRU 6 PLACES 18 4 6 6 00 152 4 192 4 88 2 156 54 77 2 54 64 5 20 5 1 87 22 1 20 5 1 TYP 1 3 5 4 2 12 ø 150 005 ø3 81 0 13 THRU 4 PLACES 199 5 06 90 22 9 3 05 77 5 4 96 126 0 25 6 4 20 5 1 20 5 1 18 4 6 2 281 57 94 ...

Страница 5: ... A E D C B A 41 10 41 6 95 176 53 6 37 161 80 5 98 151 89 5 59 141 99 5 25 133 35 4 53 115 06 3 95 100 33 3 56 90 42 3 17 80 52 2 83 71 88 2 11 53 59 1 53 38 86 1 14 28 96 75 19 05 0 25 TYP OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 1 OUTPUT 2 OUTPUT 1 S 2 76 70 1 8 32 STUD 2 PLACES E D C B A 41 10 41 2 11 53 59 1 53 38 86 1 14 28 96 75 19 05 0 25 TYP OUTPUT 1 2 76 70 1 3 07 78 0 00 2 4 12 10 32 STUD 2 PLA...

Страница 6: ...0 Output Voltage Trimming Do not trim the outputs higher than 110 of their nominal output voltage When an output is trimmed up do not exceed its maximum rated output power Operating Temperature Do not allow the FlatPAC to exceed its maximum operating temperature which is reached when the heat sink is 85 C Full power can be delivered up to this temperature Heat sink temperature is a function of the...

Страница 7: ...latPAC AC DC Switchers To receive literature or to consult an applications engineer about installation or operation of this product contact your nearest Vicor office See page 8 Bitte lesen Sie die Sicherheits Vorschriften auf Seite 8 AMP and Faston are registered trademarks of AMP Incorporated Harrisburg PA 7 Metal Terminal Drawing P N 10894 1 Terminal and Terminal Recommended Product Model Style ...

Страница 8: ...ur Die maximale Betriebstemperatur des FlatPAC Gerätes darf nicht überschritten werden Dies ist gegeben wenn der Kühlkörper eine Temperatur von 85 Grad Celsius erreicht hat Weitere Informationen Das Vicor Applications Manual und Produkt Datenblätter enthalten ausführliche Informationen über FlatPAC AC DC Wandler Fordern Sie bitte Unterlagen bei Vicor oder Ihrer nächsten Vicor Vertretung an Vicor C...

Отзывы: