INSTALLATION 

 

Location

• 

Do not install on outside wall.

• 

Do not install in areas with direct heat source.

• 

Do no install near any air discharge grill.

• 

Do not install in areas exposed to direct sunlight.

• 

Ensure Room Controller has sufficient air circulation.

• 

Ensure wall surface is flat and clean. 

Installation

1. Open unit by pulling on bottom side of  Room Controller (Figure 1).
2. Read FCC ID and IC label installed in cover before installing any wireless 

product.

3. Ensure correct side of  base faces up. 
4. Pull cables 6in (15cm) out from wall. 
5. Align base and mark location of  two mounting holes on wall (Figure 2).
6. Install anchors in wall.
7. Insert cable in central hole of  base. 
8. Insert screws in mounting holes on each side of  base.
9. Strip each wire 1/4in ( 0.6cm) from end.
10.  Insert each wire according to wiring chart (next page).
11.  Gently push excess wiring back into hole.
12.  Gently align cover to top of  base and snap in place from bottom (Figure 3).
13.  Install security screw.

•  If  replacing an existing Line Voltage FCU Controller, label the 

wires before removal of  the controller.

•  Electronic controls are static sensitive devices. Discharge 

yourself  properly before manipulating and installing the 
Room Controller.

•  A short circuit or wrong wiring may permanently damage the 

Room Controller or the equipment.

•  All VTR8300 series Room Controllers are designed for 

use as operating controls only and are not safety devices. 
Tampering with the devices or unintended application of  
the devices will result in a void of  warranty. This transmitter 
must be installed to provide a separation distance of  at least 
4in (10cm) from all persons and must not be collocated 
or operating in conjunction with any other antenna or 
transmitter.

Figure-1    Open the cover

Figure-2    Install the base

Figure-3    Reinstall cover

Содержание VTR8300 Series

Страница 1: ...Applications CONTENTS Installation 2 Location 2 Installation 2 Terminal Identification and Function 3 Communication wiring to VC3xxxE Relay Pack 3 BACnet Communication Wiring if applicable 3 Network wiring topology 3 How to Enter Setup Screen 4 Setup Screen Display 4 Specifications 5 Drawing and Dimensions 6 Version 5 ...

Страница 2: ...ow switches thermal protections and or an alarm system to protect the entire system against any catastrophic failures Tampering with the devices or unintended application of the devices results in a void of warranty If the equipment is used in a manner not specified by the manufacturer the protection provided by the equipment may be impaired These devices are not serviceable and must be returned t...

Страница 3: ...on each side of base 9 Strip each wire 1 4in 0 6cm from end 10 Insert each wire according to wiring chart next page 11 Gently push excess wiring back into hole 12 Gently align cover to top of base and snap in place from bottom Figure 3 13 Install security screw If replacing an existing Line Voltage FCU Controller label the wires before removal of the controller Electronic controls are static sensi...

Страница 4: ...ler All other slave units must be VC3xxxE Relay Pack s WITHOUT remote inputs A maximum of 10 VC3xxxE Relay Packs can be used for a single VTR83xxA Room Controller From VTR83xxA to first VC3xxxE Relay Pack Uses existing or new field wires A minimum of 3 wires are required 14 22 Ga Solid or Stranded shield not necessary From first VC3xxxE to all other slave VC3xxxE Relay Pack s Uses existing or new ...

Страница 5: ...ctions such as Date Time Humidity Outdoor Temperature Setpoint and others to be enabled or disabled by setting various parameters Time System Status Fan Status Up Arrow Increase Temperature Setpoint Actual Setpoint Down Arrow Decrease Temperature Setpoint Help Language Selection Temperature Units Fan Mode Date Occupancy Status Indoor Temperature Indoor Humidity Outdoor Temperature System Mode Shor...

Страница 6: ... 3 seconds to enter setup mode Note If a configuration installer password is activated to prevent unauthorised access to the configuration menu parameters a password entry prompt will appear to prevent access to the device configuration components Discover Mode The Controller will become discoverable on the wireless ZigBee network for 1 minute this button is hidden if ZigBee settings are not confi...

Отзывы: