Screw terminal arrangement 

 

Main outputs wiring  

 

Wiring notes: 
 
Note 1:  If the same power source is used for the heating stages, install jumper across RC & 

RH.  Maximum current is 2.0 amps. 

Note 2:  If auxiliary output is used to toggle occupancy of the electronic control card inside 

the equipment, configure the relay parameter (Aux cont) to the N.O. setting.  A 
second relay can be added for additional functionality of the occupancy output. 

Note 3:  Economizer output uses a half bridge rectifier.  Reference of the control signal is the 

common of the power supply of the Room Controller. (Terminal C) 

Note 4:  Electromechanical contacts are to be used with the digital inputs.  Electronic triacs 

cannot be used as mean of switching for the input.  The switched leg to the input for 
the input to activate is terminal C (common) 

Note 5:  The transformer of the unit provides power to the t Room Controller and the 

additional loads that will be wired to the Room Controller. 

 

 

 

EC AU D1 D2 RS

Scom

OS MS

Y2 Y1

G

RC C

RH W1

W2

O/B

5 pole left top connector

3 pole left top connector

8 pole bottom connector

Содержание VT7600 Series

Страница 1: ...tion 4 Wiring 4 Screw terminal arrangement 5 Main outputs wiring 5 Typical applications 6 Remote sensor accessories 7 Configuring and Status Display Instructions 9 Status display 9 User Interface 12 12 User configuring instructions menu 12 Local keypad interface 12 VT7600 Series Installation Guide November 2015 ...

Страница 2: ...5 Nothing should restrict vertical air circulation to Room Controller Installation 1 Swing open Room Controller PCB to left by pressing PCB locking tabs fig 2 2 Pull out cables 6 out from wall Ensure wall surface is flat and clean 3 Insert cable in central hole of base 4 Align base and mark location of two mounting holes on wall ensuring proper side of base is up 5 Install anchors in wall 6 Insert...

Страница 3: ...troller or the equipment All VT7000 series Room Controllers are designed for use as operating controls only and are not safety devices These instruments have undergone rigorous tests and verification prior to shipping to ensure proper and reliable operation in the field Whenever a control failure could lead to personal injury and or loss of property it becomes the responsibility of the user instal...

Страница 4: ... Top left terminal block Y2 X X X X Y2 X X Y1 X X X X X X Y1 X X G X X X X X X G X X RC X X X X X X RC X X C X X X X X X C X X Top right terminal block Top right terminal block RH X X X X X X RH X X W1 X X X X X X W1 X X W2 X X X X O B X X Bottom terminal block Bottom terminal block Econo X X Aux X X X X X X Aux X X DI1 X X X X X X DI1 X X DI2 X X X X X X DI2 X X RS X X X X X X RS X X Scom X X X X...

Страница 5: ...output Note 3 Economizer output uses a half bridge rectifier Reference of the control signal is the common of the power supply of the Room Controller Terminal C Note 4 Electromechanical contacts are to be used with the digital inputs Electronic triacs cannot be used as mean of switching for the input The switched leg to the input for the input to activate is terminal C common Note 5 The transforme...

Страница 6: ...xiliary Output O B AU DI1 DI2 Scom RS Remote Outdoor Sensor Remote Mixed Air Sensor MS OS Controller Terminals VT7652H5x00 Y2 DI1 DI2 AU Y1 RC G O B OS RS Scom RH C W1 MS Heat Stage 2 Cool Stage 1 System wiring Thermostat internal wiring Jumper J1 T1 24 Vac Cool Stage 2 Y2 Y1 Jumper J1 See note 1 previous page Fan RC G C Heat Stage 1 W1 RH W2 Auxiliary Output Field contacts Com 24V Remote Outdoor ...

Страница 7: ...uct mounted temperature sensor Remote mount temperature sensors use 10K NTC thermistor This sensor can be used for Various averaging combinations Optional occupancy led Optional override key Wall mounted sensor WIRING EXAMPLE OF SINGLE REMOTE ROOM SENSOR AU D1 RS Scom C D2 Scom RS Scom RS C DI Aux Scom RS Scom RS OR VT7600 Series 1x S3020W1000 Remote wiring 1 sensor S2 1 ON S2 2 ON S3010W1000 Remo...

Страница 8: ...itch setting in each remote sensor A U D 1 R S S c o m C D 2 S c o m R S S c o m R S C D I A u x S c o m R S S c o m R S C D I A u x A U D 1 R S S c o m C D 2 S c o m R S S c o m R S S c o m R S S c o m R S C D I A u x VT7600 Series 2x S3020W1000 Remote wiring 2 sensors S2 1 OFF S2 2 ON A U D 1 R S S c o m C D 2 S c o m R S S c o m R S S c o m R S S c o m R S 2x S3010W1000 Remote wiring 2 sensors ...

Страница 9: ...4182 52 126 3 3568 27 17 142 7211 7 19 46 1933 13 55 17 1440 33 91 7 1150 53 127 3 2333 26 15 134 3971 6 21 43 8268 14 57 16 3665 34 93 6 8259 54 129 3 1150 25 13 126 6109 5 23 41 5956 15 59 15 6286 35 95 6 5499 55 131 3 0016 24 11 119 3244 4 25 39 4921 16 61 14 9280 36 97 6 2866 56 133 2 8928 23 9 112 5028 3 27 37 5056 17 63 14 2629 37 99 6 0351 57 135 2 7886 22 8 106 1135 2 28 35 6316 18 64 13 6...

Страница 10: ...atus display of 50 C 122 F indicates a shorted sensor Associated functions such as mode lockouts and economizer function are automatically disabled A minimum range status 40 C 40 F is not displayed and indicates a opened sensor or a sensor not connected Associated functions such as mode lockouts and economizer function are automatically disabled Alarms If alarms are detected they will automaticall...

Страница 11: ...er cover are used to indicate the status of the fan a call for heat or a call for cooling When any of the fan is ON the FAN LED will illuminate When heating is ON the HEAT LED will illuminate When cooling is ON the COOL LED will illuminate LED OPERATION HEATPUMP MODELS VT76XXH MULTISTAGE AND SINGLE STAGE MODELS VT7600A VT7652A VT7600B VT7652B MULTISTAGE ECONOMIZER MODELS VT7605B VT7656B Fan LED on...

Страница 12: ...om Controller Ex Press yes key to change cooling temperature setpoint Use the up or down arrow to adjust cooling setpoint Local keypad interface Each of the sections in the menu is accessed and configured using 5 keys on the Room Controller cover The priority for the alarms is as follows The YES key is used to confirm a selection to move onto the next menu item and to manually scroll through the d...

Страница 13: ...13 028 0228 06 November 2015 Viconics Technologies Inc Tel Fax Toll free www viconics com ...

Отзывы: