VC3000 Series
6
Installation Guide
Viconics Technologies Inc.
www.viconics.com [email protected]
028-0296-10
April 2019
MODEL CHART
Part #
VC3500E5000 VC3504E50400 VC3514E5000
Occ. Output VC3400E5000 VC3404E5000
VC3300E5000
Slave Fan
Unit
Applications
2 pipes
2 pipes with
reheat
4 pipes
2 pipes
2 pipes with
reheat
4 pipes
2 pipes
2 pipes with
reheat
4 pipes
2 pipes
2 pipes with
modulating
pulsed reheat
2 pipes
2 pipes with
modulating
pulsed reheat
Slave fan
control only
Fan control
Up to 3 speed
Up to 3 speed
Up to 3 speed
Up to 3 speed
Up to 3 speed
Up to 3 speed
Monitoring
inputs
None
4 FCU remote
inputs
4 FCU remote
inputs
None
4 FCU remote
inputs
None
Control
types
On-Off line
switched valve
output control
-
1 heat / cool
output
-
1 cool output
-
3 fan outputs
On-Off line
switched valve
output control
-
1 heat / cool
output
-
1 cool output
-
3 fan outputs
On-Off line
switched valve
output control
-
1 heat / cool
output
-
1 cool output
-
3 fan outputs
-
Occupancy
output
(7VDC)
On-Off line
switched valve
output control
-
1 heat / cool
output
-
1 Modulating
pulsed Vdc
output for
SSR electric
reheat
control
-
3 fan outputs
On-Off line
switched valve
output control
-
1 heat / cool
output
-
1 Modulating
pulsed Vdc
output for
SSR electric
reheat
control
-
3 fan outputs
Slave fan
control only
3 fan outputs
Ordering Information Notes:
• Please refer to the “Operation overview” section for related information on VTRX3xxA and VC3xxxE
arrangements and possible combinations.
• More than one VC3xxxE Relay Pack can be used for a single VTRX3xxA Terminal Equipment Controller.
• Only one VC3x4X Relay Pack with monitoring input can be used for a single VTRX3xxA Terminal Equipment
Controller.
Ordering examples:
• A VC3500E5000 is for a 90 to 277 Vac powered, FCU-mounted relay pack with the following outputs:
Three 90 to 277 Vac switching fan relay outputs
Two 90 to 277 Vac switching valve relay outputs
• A VC3504E5000 is for a 90 to 277 Vac powered, FCU-mounted relay pack with the following inputs and
outputs:
One configurable universal input
One configurable binary input
One dedicated discharge air temperature monitoring input
One dedicated return air temperature control input
Three 90 to 277 Vac switching fan relay outputs
Two 90 to 277 Vac switching valve relay outputs
• A VC3300E5000 is for a 90 to 277 Vac powered FCU-mounted relay pack with the following outputs:
Three 90 to 277 Vac switching fan relay outputs