Temperature and Humidity
1.
A well maintained room temperature and humidity is essential for proper Kollector operation. An air-
conditioned (A/C) environment is required so a continuous supply of cool and dry air is available.
Ideal Kollector operation occurs at a room temperature range of 66 - 77
˚
F (19 - 25
˚
C) and must not
exceed a range of 50 - 86
˚
F (10 - 30
˚
C). The ideal room humidity should not exceed 80% non-
condensing relative.
2.
When calculating HVAC requirements, a good cooling load estimate for each Kollector units is about
30 BTU/min (7 Kg-cal/min), based on a 500 watt load. However, a better cooling load estimate is
based on the addition of a monitor and UPS. This would be about 100 BTU/min (25 Kg-cal/min).
Typical Kollector Rack Installation
8
•
Environmental Requirements
XX112-70-00 Rev 904 Kollector Pre-Installation Requirements