Inspect and clean connectors 

Before connecting a fiber into a test module or fiber panel, inspect and clean the bulkhead and the fiber jumper connectors. 

1. 

Connect the P5000i video inspection scope to both units USB port (any)  

2. 

Press the 

 hard key on the both units to turn-up. 

3. 

Press the 

    hard key on the T-BERD/MTS 8000 

4. 

Press the 

    hard key on the T-BERD/MTS 6000A or 

 if 6000AV2 

5. 

Activate the Microscope 

 function on both units by touching twice with your finger or stylus. 

6. 

Use the P5000i video inspection scope to verify the connector quality. 

 

7. 

Use appropriate cleaning material (e.g. IBC™ cleaner, cotton swab, dust air sprays, etc...) and re-inspect to confirm. 

Activating the CD function on the T-BERD/MTS 8000 unit 

1. 

Press the 

 hard key to turn-up. 

2. 

Press the 

 hard key when unit is on.  

3. 

Activate the 

 test functions by touching twice with your finger or stylus. Wait for the tuning process of the 

DISAP module (~1min.) 

1. 

Press the 

 key and touch the 

 tab 

2. 

Select 

 

Connecting both test sets 

1. 

Inspect and clean connectors of the fiber jumpers, the COM port of the T-BERD/MTS 8000 and the OTDR port of the 
T-BERD/MTS 6000A using the P5000i inspection scope. 

2. 

Connect the fiber jumper 1 to the T-BERD/MTS 8000 COM port of the MTAU module and to the mating adapter. 

3. 

Connect the fiber jumper 2 to the T-BERD/MTS 6000A OTDR module and to the mating adapter. 

 

HOME 

ON 

OFF 

SYSTEM 

HOME 

Patchcord inspection 

Bulkhead and test port inspection 

RESULTS 

HOME 

ON 

OFF 

T-BERD/MTS 8000 

T-BERD/MTS 6000A 

8000V2 Platform - Fiber Characterization Quick Card FC4 – V1.3 - Oct 2015 – 

Copyright 2015 VIAVI Solutions. All rights reserved

 

Содержание T-BERD/MTS 8000

Страница 1: ...is measurement is done to ensure that the broadband source is taken into account for an accurate qualification of the fiber to test This procedure is a two ended test Note 1 Both products must be at the same location Note 2 it is possible to apply a new reference to an existing CD result Please read the entire procedure BEFORE starting 8000V2 Platform Fiber Characterization Getting Started V1 3 Oc...

Страница 2: ...D MTS 8000 unit 1 Press the hard key to turn up 2 Press the hard key when unit is on 3 Activate the test functions by touching twice with your finger or stylus Wait for the tuning process of the DISAP module 1min 1 Press the key and touch the tab 2 Select Connecting both test sets 1 Inspect and clean connectors of the fiber jumpers the COM port of the T BERD MTS 8000 and the OTDR port of the T BER...

Страница 3: ...00 1 Press the hard key 2 Touch the tab 3 Select 4 Enter the BBS serial number under Note BBS serial number is displayed on the T BERD MTS6000A Results page 5 Press the key 6 Confirm by pressing YES when the message pops up Note A message valid Reference is displayed in green If not verify proper connector cleanliness and interconnections then restart referencing process SETUP SART STOP HOME SYSTE...

Страница 4: ...ed For example 3 Highlight the file that has the requested T BERD MTS 6000A reference 4 Press the soft key 5 Select Loading the trace configuration will take you to the results page 6 Press the hard key Note You now see 2 reference boxes On says and that shows the current reference loaded into the test unit The lower box says and that shows the reference information for the trace that is currently...

Отзывы: