8380 RPC User’s Guide
Document Num., Rev. 3
May 2018
Page 14
Installing the 8380 RPC
The following section explains the procedure used to physically install the 8380 RPC. In order
to properly setup the 8380 RPC the following steps must be completed in this order. Do not
skip any steps.
DO NOT plug in the power cord of the 8380 RPC until
instructed below.
If the Power LED is not illuminated upon connecting power to
the 8380 RPC, contact 1-844-GO-VIAVI for assistance.
Upon reboot (regardless of source/cause), the master 8380
RPC will load the last saved device settings, system settings,
user settings, and network configuration as well as deactivate
all ports present in the 8380 RPC system.
1. Mount the 8380 RPC in a standard rack using four retaining screws.
2. Connect an ethernet cable to the master unit.
3. Connect the RS-485 cables and set the addresses and terminations of the master and
slave units accordingly.
4. Plug the AC to DC Power Adapter of the 8380 RPC into the
Power Input
and then into
an AC power source. When power is supplied to the 8380 RPC, the Power LED on the
front panel of the unit will illuminate.
5. When the unit is ready for operation, the Status LED on the front panel of the unit will
illuminate.