ArcLight Hub User’s Guide
Component Operating Procedures
5-110 1081006
Rev.
001
5.28 ArcLight System Racks
5.28.1 Rack Dimensions
The ArcLight Hub equipment resides in a standard 19 in. rack, with a
height of 44RU and a depth of 41 in., as shown in Figure 5-80. Two
racks are required to house all Hub equipment.
5.28.2 Mounting
Holes are located in the bottom of the rack to allow securing it to the
facility floor to reduce movement in the event of seismic activity. ViaSat
recommends using threaded rods and Uni-struts to secure the rack to
the tile floor. The racks must be secured to a concrete sub-floor.
5.28.3 Cooling
The ArcLight Hub racks are designed to operate between 15 degrees C
and 35 degrees C, and to maintain less than 15 degrees C temperature
rise inside a rack. An average of approximately 15000 Btu/hr of heat
dissipation is expected from the ArcLight Hub. An estimate of 1500
CFM of airflow is required for cooling the rack.
Figure 5-80. ArcLight System Cabinets.
Содержание ArcLight
Страница 2: ......
Страница 3: ...ArcLight TM Hub User s Guide ViaSatDocument Number 1081006 Rev 001 ...
Страница 4: ......
Страница 5: ...ArcLightTM Hub User s Guide ...
Страница 6: ......
Страница 7: ...ArcLight TM Hub User s Guide ViaSatDocument Number 1081006 Rev 001 ...
Страница 9: ......
Страница 10: ......
Страница 12: ...ArcLight Hub User s Guide iv 1081006 Rev 001 ...
Страница 35: ...ArcLight Hub User s Guide Rev 001 1081006 xxvii ...
Страница 36: ......
Страница 64: ...ArcLight Hub User s Guide General System Description 1 28 1081006 Rev 001 ...
Страница 70: ...ArcLight Hub User s Guide Initial Network Configuration 2 6 1081006 Rev 001 ...
Страница 237: ...ArcLight Hub User s Guide Screen Descriptions for NMS Client Rev 001 1081006 3 167 ...
Страница 238: ......
Страница 364: ...ArcLight Hub User s Guide A 2 1081006 Rev 001 ...
Страница 366: ...ArcLight Hub User s Guide B 2 1081006 Rev 001 ...
Страница 368: ...ArcLight Hub User s Guide I 2 1081006 Rev 001 ...