19
The sockets are connected in a way making sure that the protection plug is at the top and the phase
conductor is connected to the left tube when viewed from the front. The same applies to the double
sockets.
7.2 Boilers commissioning
1. Fire the boilers (see chap.8.3.).
2. Bring the boiler to the necessary operating temperature. Recommended temperature of outlet heating
water is between 60 and 90°C.
3. Check again visually the boiler tightness.
4. Carry out the stoking test according to relevant standards (see the guarantee certificate)
5. Make the user acquainted with boiler operation (see chap.8).
6. Make a record in guarantee certificate.
8. Boiler operation by user
8.1 MONEX regulator
The regulator is positioned in an unified compact plastic box. Under the plastic cover able to open there is
the frontal panel which consists of the main circuit breaker, keyboard and indication elements.
#
9
0
8
*
7
4
1
2
3
6
5
0
I
Automatics for biomass combustion boilers
k
k l
l
á í bi
Outlet
water
temp.
°C
6
5
4
8
7
2
1
3
STOP
Inhib.
manual
automat
Functions on keyb.
Emergency
thermostat
6 - max.inhib.time
7 ventilator drifting
* - setting
# - START automat
1 , 2 - STOP automat
1 - ventilator
2 – fuel feeder
3 – req. outlet water temp.
4 – feeder on
5- feeder off
9
Fig.no.16 MONEX regulator control panel
It enables the settings as follows:
•
Outlet heating water temperature
•
Automatic regime of screw conveyors and ventilator
•
Parameters for inhibited regime
•
screw conveyor and ventilator manual operation
It is equipped with an inlet for indoor thermostat. It ensures the circulating pump operation (the pump is
put into operation after the heating water temperature of 40 °C has been exceeded) and its after-running
before switching off.
The regulator ensures an automatic
drifting of
combustion chamber
screw conveyor i
n that sense,
that after every fuel reservoir screw conveyor stop the combustion chamber screw conveyor keeps working
for another 8 seconds.
1 – main switch, fuse6A
2 – emergency
thermostat cover
3 – left part of display -
output water
temperature display
4 – right part of display -
operating status
display
5 – keyboard
6 – instructions for
keyboard use
7 - ventilator symbolu
8 – fuel symbol
9 – pump symbol