Test Mode for IR Function   

  The Smoke Detector can be put into Test mode by pressing the Test Button. Every time the Test Button is pressed, the Smoke 

Detector will transmit a test signal to the Control Panel for radio range test and enter the test mode for 3 mins. It will exit Test Mode 
automatically after 3 minutes and return to normal mode. In Test mode, the sleep timer is disabled, and the LED indicator will flash 
every time a movement is detected. 

 

Supervision 

  The Smoke Detector will transmit a supervision signal to report its condition regularly according to user setting. The factory default 

interval is 30~50 minutes. The user can also press the Test Button once to transmit a supervision signal manually. 

 

(SD-29-H/SD-29-HM/SD-29-HME only)

Temperature Detection 

 

  The Temperature Sensor measures temperature every 10 seconds, and transmits temperature reading to the Control Panel every 

30~33 minutes. 

  Users can also press the Test Button once to transmit current temperature reading manually. 

 

Alarm Activation

   

The Smoke Detector will activate fire alarm when either of its smoke detection or high heat detection function is triggered. When an 
alarm is activated, the Smoke Detector will transmit alarm signal and raise alarm with its built-in buzzer.   

Smoke Detection: 

  The Smoke Detector checks smoke concentration every 8 seconds 

  The alarm is activated whenever the smoke concentration exceeds the detection threshold, and will continue until the smoke 

concentration drops below alarm threshold. 

  The Red LED will flash quickly during alarm. 

Heat Detection:

 

(SD-29-H/SD-29-HM/SD-29-HME only)

 

  The Smoke Detector checks temperature every 10 seconds. The alarm will be activated in the following conditions: 

- When the temperature rises by 8.25°C per minute (Rate of Rise). 
- When the temperature exceeds 57.25°C (High Heat). 

  The Red LED will flash every second during alarm. The Smoke Detector will only stop alarming if the temperature drops below 

alarm threshold: 

  If the alarm was triggered by Rate of Rise condition (8.25°C per minute or more), the temperature must drop to 4°C below highest 

temperature detected for the detector to stop alarming. 

  If the alarm was triggered by High Heat condition (57.25°C), the temperature must drop below 49°C for the Smoke Detector to 

stop alarming. 

  The Smoke Detector will transmit a restore signal if no smoke or high heat is detected for 160 seconds. 

  If the alarm condition persists, the Smoke Detector will resend alarm signal every 2 minutes. 

         

IR Detection: (SD-29-M/SD-29-HM/SD-29-HME only)

 

  The Smoke Detector will transmit signal to the Control Panel if any movement is picked up within the IR detection coverage. The 

buzzer will not sound and the LED will not flash. Please refer to your Control Panel for details. 

 

Emergency Light 

(SD-29-HME only)

 

  The Smoke Detector has a built-in emergency light that can provide visual alerts in case of emergency. When the Smoke Detector 

is activated, the emergency light will begin to flash slowly to indicate the system is alarming. 

 

 

Serial Connection  

  The Smoke Detector is in serial connection with other Smoke Detector in the alarm system. When a Smoke Detector activates 

alarm, the Control Panel will notify other Smoke Detectors to also raise alarm even if they have not detected smoke yet. The 
alarm length will be in accordance with the Control Panel’s setting. 

  You cannot press the function button to silence alarm activated by other Smoke Detectors. 

  Alarm will be restored only after 3 minutes timeout or until the other Smoke Detector which triggers alarm transmits a restore 

signal. 

 

Alarm Silence 

  When the Smoke Detector is alarming, pressing the Test button will put the Smoke Detector into Alarm Silence mode to silence 

the alarm for 9 minutes. The buzzer will only stop sounding after the alarm has been activated for at least 1-minute. If the button is 
pressed before alarm time reaches 1 minute, the Smoke Detector will wait until alarm time has reach 1 minute before silencing the 
alarm. 

  During the 9-minute Alarm Silence period, the Red LED will flash once per second. The Smoke Detector will continue to monitor 

smoke concentration during the alarm silence period: 

  After the 9-minute Alarm Silence period has expired, if the smoke concentration has dropped below alarm threshold, the Smoke 

Detector will emit a 2-tone beep and return to normal operation without sounding alarm. 

  If smoke concentration still exceeds alarm threshold, the Smoke Detector will start alarming again. 

  If smoke concentration continues to rise during Alarm Silence period and exceeds a second alarm threshold, the Smoke Detector 

will start alarming again. An alarm activated by exceeding the second alarm threshold could not be silenced by pressing the test 
button.

 

 

Recalibration 

As the operation condition of the Smoke Detector may vary after being installed for some time, you may wish to recalibrate the Smoke 
Detector to take a new smoke detection threshold value and ensure optimal performance of the Smoke Detector. To do this: 

  Press and hold the Test Button for 10 seconds and release when the Smoke Detector emits 2 beeps. The device will sound 

another beep after 5 seconds and begin calibration. The Red LED will flash every 2 seconds to indicate. 

  Calibration process lasts 1~9 minute. 

  When calibration is finished, the Smoke Detector will sound a two-tone beep. The Red LED will stop flashing to indicate it has 

returned to normal mode. 

  If calibration fails, the Smoke Detector will beep continuously, and the Orange LED will flash every 5 seconds. Please remove the 

battery, press the Test Button twice to fully discharge, and then reinsert the batteries to restart Smoke Detector. 

Содержание SD-29-SC-AC Series

Страница 1: ...flash Alarming Flashes every 1 second Smoke Detector under Sleep Mode Flashes every 2 seconds Smoke Detector under warmup and calibration process Flashes every 4 seconds with Orange LED battery exhausted Flashes briefly When Learn Button is pressed to see if the device is functioning normally Turns ON briefly Transmitting signal Orange LED Flashes every 4 seconds with RED LED battery exhausted Fla...

Страница 2: ...igure 2 Step 5 Repeat Step 3 and Step 4 to insert the black wire Inserting the two wires to the same side right as shown below of the two connectors provide an easier installation in the following steps Step 6 Insert the AC wires to the two connectors respectively as shown below Use a pair of tweezers to turn the Battery Switch to ON position the rechargeable battery will begin to charge Figure 3 ...

Страница 3: ...Control Panel for details Emergency Light SD 29 HME only The Smoke Detector has a built in emergency light that can provide visual alerts in case of emergency When the Smoke Detector is activated the emergency light will begin to flash slowly to indicate the system is alarming Serial Connection The Smoke Detector is in serial connection with other Smoke Detector in the alarm system When a Smoke De...

Страница 4: ...n be received by the Control Panel at mounting location Step 2 Take out the mounting sheet included in the package The picture s size equals the Smoke Detector s actual size and the perforated design allows for easy tear off after installation Step 3 Position the sheet tight against the ceiling and use the four holes as template to drill holes and insert wall plugs if required Ensure the wall plug...

Отзывы: