VESDA by Xtralis
VESDA VLP Product Guide
www.xtralis.com
31
8
Backup Battery
The power supply for the VESDA VLP detector is switched to a back up battery in the event of a mains power
supply disruption. The size of the back up battery is determined by local standards and codes, the total power
required by the system, back up time required, allowance for reduction in capacity with age and expected
temperature variations.
Note:
It is recommended that batteries be inspected and changed as per manufacturer’s specifications or
as per your local codes and standards.
To facilitate the calculation of the backup battery size a Battery Calculation Sheet is included below.
Equipment
Normal loads @ 24 V DC
Full alarm load @ 24 V DC
Load mA
Qty
Total
Load mA
Qty
Total
Detector @ 3000 rpm
240
290
Detector @ 3500 rpm
280
330
Detector @ 4000 rpm
320
370
Detector @ 4200 rpm
340
390
Integral Display
60
80
Integral Programmer
20
(backlight off)
80
(backlight on)
Remote Display
90
110
Remote Programmer
50
(backlight off)
110
(backlight on)
Hand-held Programmer 50
(backlight off)
110
(backlight on)
System Relay Module
60
105
Remote Termination
Card - 7 Relays
60
105
Other 24V Loads
Total
mA
Total
mA
X
X
Standby Hours
Alarm Hours
=
Standby Capacity
Alarm Capacity
Total Capacity =
S Alarm
Divided by 1000 for
Standby Capacity
Multiply by battery
factor X1.25
Table 8-1: Calculating the size of backup battery
Note:
If the intelligent VESDA power supply is fitted it will report power failures (F15) on VESDAnet.
VESDA VLP & VESDA VLS with GPI terminals connected will maintain their aspirator speed for an
hour after the loss of mains power. After which, the aspirator speed will be limited to 3000 rpm to
conserve power.
Содержание VLP
Страница 1: ...VESDA VLP Product Guide September 2014 Document 10278_09 Part Number 19145 ...
Страница 2: ......
Страница 8: ...VESDA VLP Product Guide VESDA by Xtralis 2 www xtralis com This page is intentionally left blank ...
Страница 10: ...VESDA VLP Product Guide VESDA by Xtralis 4 www xtralis com This page is intentionally left blank ...
Страница 16: ...VESDA VLP Product Guide VESDA by Xtralis 10 www xtralis com This page is intentionally left blank ...
Страница 24: ...VESDA VLP Product Guide VESDA by Xtralis 18 www xtralis com This page is intentionally left blank ...
Страница 28: ...VESDA VLP Product Guide VESDA by Xtralis 22 www xtralis com This page is intentionally left blank ...
Страница 34: ...VESDA VLP Product Guide VESDA by Xtralis 28 www xtralis com This page is intentionally left blank ...
Страница 36: ...VESDA VLP Product Guide VESDA by Xtralis 30 www xtralis com This page is intentionally left blank ...
Страница 38: ...VESDA VLP Product Guide VESDA by Xtralis 32 www xtralis com This page is intentionally left blank ...
Страница 42: ...VESDA VLP Product Guide VESDA by Xtralis 36 www xtralis com This page is intentionally left blank ...
Страница 52: ...VESDA VLP Product Guide VESDA by Xtralis 46 www xtralis com This page is intentionally left blank ...