4.4
Locating cables connected to a grounded object
To locate a cable connected to a grounded
object, connect one SG33 output to the
object itself. Ground the second output in
the opposite direction from the located
cable with a grounding rod as far as
possible. If soil is inaccessible, ground the
second output to another nearby grounded
object that is not connected to the located
cable.
Boost mode is recommended if the other
end of the cable has poor or no connection
to ground or the soil is dry. It is possible to locate multiple cables connected to the same
grounded object with this method.