BASIC RACK PDU 

 

 

Installation 

 

Instructions 

 

1.  Using appropriate hardware, mount PDU to rack (see 

Mounting

 section for additional 

instructions. 

2.  Plug PDU into de-energized 30 Amp branch circuit receptacle.** 
3. 

Connect devices into PDU’s output receptacles. It is recommended that the devices are 
turned off until all devices are connected to PDU 

 

4.  Turn on branch circuit to energize PDU. 
5.  Power on devices. Sequential power up is recommended to avoid high inrush current. 

 
 

**Branch Circuit should be sized based on the PDU’s nameplate electrical rating. A 24 Amp 

rated PDU is intended for use on a 30 Amp Branch Circuit. For Global Units a 32 Amp rated 
PDU is intended for use on a 32 Amp Branch Circuit. 

 

Guidelines 

 

 

If the PDU is installed in a cabinet the ambient temperature of the rack should be no greater 
than 45

C.

 

Install the PDU such that the amount of airflow required for safe operation of equipment is not 
compromised.

 

Mount the PDU so that a hazardous condition is not achieved due to uneven mechanical 
loading.

 

Follow  nameplate  ratings  when  connecting  equipment  to  the  branch  circuit.  Take  into 
consideration the effect that overloading  of the circuits might have on over-current protection 
and supply wiring.

 

The  PDU  relies  on  the  building  installation  for  protection  from  over-current  conditions.  A 
certified  overcurrent  protection  device  is  required  in  the  building  installation.  The  overcurrent 
protection device should be sized according to the PDU’s nameplate ratings and local/national 
electrical codes.

 

Reliable  earthing  of  rack-mount  equipment  should  be  maintained.  Particular  attention  should 
be  given  to  supply  connections  other  than  direct  connections  to  the  branch  circuit.  The  PDU 
must be connected to an earthed socket-outlet.***

 

The PDU is intended for Restricted Access Locations only and only qualified service 
personnel should install and access the PDU.

 

For pluggable equipment, install the PDU so that the input plug or appliance coupler may be 
disconnected for service.

 

Sequential power-up of devices powered by the PDU is recommended to avoid high inrush 
current.

 

Caution: 

Disconnect all power cords before servicing.

 

The PDU is intended for use with TN, TT, or IT power supply systems

 
 
 

***XP Series PDUs may optionally be configured as Isolated Ground units. All Isolated 

Ground units will be shipped with an enclosure grounding cable. This cable must be 
connected between the enclosure and a reliable safety ground. 

  
 

Содержание VP7541

Страница 1: ...Instruction Manual Basic Rack PDU VP7541 and VP9571A VertivCo com geist ...

Страница 2: ...re 3 Humidity 3 Elevation 3 Electrical 3 Receptacle Ratings 3 EMC Verification 3 Installation 4 Instructions 4 Guidelines 4 Mounting 5 Optional Local Monitoring 12 Power Meter 12 Current Meter 12 Service Tech Support 13 Service and Maintenance 13 More Technical Support 13 ...

Страница 3: ...000 m 6561 ft max Storage 0 m 0 ft min 15240 m 50000 ft max Electrical See nameplate for unit ratings Receptacle Ratings NEMA 5 15R or L5 15R 125 Volts 15 Amp NEMA 5 20R or L5 20R 125 Volts 20 Amp NEMA 6 20R or L6 20R 250 Volts 20 Amp IEC 320 C13 125 250 Volt 15 Amp per Receptacle Bank IEC 320 C19 125 250 Volt 20 Amp EMC Verification This Class A device complies with part 15 of the FCC Rules Opera...

Страница 4: ...he effect that overloading of the circuits might have on over current protection and supply wiring The PDU relies on the building installation for protection from over current conditions A certified overcurrent protection device is required in the building installation The overcurrent protection device should be sized according to the PDU s nameplate ratings and local national electrical codes Rel...

Страница 5: ...BASIC RACK PDU 5 Mounting Full Length Bracket Using the full length bracket mount PDU to rack as shown Mini L Brackets SLB 4 ...

Страница 6: ...al Extension Brackets VCB 1 Using the vertical extension brackets attach PDU to rack as shown Toolless Mounting Hardware 11621 Secure toolless mounting buttons to PDU as shown Use toolless buttons with key holed slots built into cabinet or with optional Vertiv key holed brackets ...

Страница 7: ...acket TLFL Using full length toolless bracket and toolless mounting buttons attach PDU to rack as shown Single Side Mount 2 Unit Brackets TSMX2 Using single side mount 2 unit brackets and toolless mounting buttons attach PDU to rack as shown ...

Страница 8: ...BASIC RACK PDU 8 Offset Side Mount Brackets EZB 1 Using the offset side mount brackets attach PDU to rack as shown 7 Extension Brackets XB 7 Using the 7 extension brackets attach PDU to rack as shown ...

Страница 9: ...BASIC RACK PDU 9 Flush Mount Brackets FM Using flush mount brackets attach PDU to rack as shown Adjustable Mount Brackets AM Using adjustable mount brackets attach PDU to rack as shown ...

Страница 10: ...ASIC RACK PDU 10 Panel Mount Brackets PM Using panel mount brackets attach PDU to rack as shown 23 Conversion Mounting Brackets 23 RM Using conversion mounting brackets attach 19 PDU to 23 rack as shown ...

Страница 11: ...able Mount Bracket CMB 1 Attach cable mount bracket to PDU as shown use tie wraps to secure cords to bracket 19 Horizontal Panel Mount Brackets 7938 Using the 19 horizontal panel mount brackets attach PDU to rack as shown ...

Страница 12: ...ured in true RMS Amps Voltage PDU output voltage measured in true RMS Voltage Power PDU output power measured in Watts referred to as real or active power Power Factor Ration of real PDU output power to apparent PDU output power Power Meter Display Real power is the power in a circuit that is transformed from electric to non electric energy while apparent power is the total power supplied to the c...

Страница 13: ...U or you may void the warranty No serviceable parts inside It is recommended that power be removed from the unit before installing or removing any equipment More Technical Support VertivCo com geist Phone Support 1 800 432 3219 Email support VertivCo com or contact your distributor Technical Support Form vertivco com Tech Support ...

Страница 14: ...BASIC RACK PDU 14 Thank You For Purchasing Your Vertiv Product VertivCo com geist ...

Отзывы: