4.4 Vertiv™ SmartRow™ DCX Equipment Placement within the Row
4.4.1 Cooling Unit and Rack Placement
•
Server (600mm wide) and Networking (800mm wide) racks are treated equally and generically referred to as
“racks.”
•
When determining the location for Liebert® CRVs within the row, they should be evenly spaced within the rack
lineup to maintain uniform airflow distribution, assuming that the heat-load density is fairly uniform across all of
the racks. If there are a couple of racks within the row with a higher concentration of heat, Liebert® CRVs may
be placed closer to that equipment.
•
Do not place two Liebert CRV cooling units next to each other.
•
UPS placement does not influence the placement of the cooling units due to the relatively low heat and air-flow
demands of the UPS system.
•
If the cooling system is designed for N+1 redundancy, be sure that each rack is within the region of influence of
2 or more Liebert CRVs with sufficient capacity. This will ensure that if any cooling unit fails, another unit will be
able to condition the IT equipment.
•
Do not place a Liebert CRV at the end of a row next to a UPS because this would put the Liebert CRV too far
from the rack-mounted IT equipment (see
Do not locate Liebert CRV at end of row next to UPS system
below).
Figure 4.2 Do not locate Liebert CRV at end of row next to UPS system
4.4.2 UPS System
•
Two UPS systems can be located next to each other.
•
Three-phase, row-based UPS systems must be placed at the left end of the row (when viewed from the front,
cold side) to ease addition of battery cabinets to the UPS system in the future.
•
Battery cabinets can be remotely located, but they will not be conditioned by the row-based cooling system.
Vertiv
| SmartRow™ DCX Installation Manual |
14
Содержание SmartRow DCX
Страница 1: ...Vertiv SmartRow DCX Installation Manual...
Страница 6: ...Vertiv SmartRow DCX Installation Manual 6 This page intentionally left blank...
Страница 8: ...Vertiv SmartRow DCX Installation Manual 8 This page intentionally left blank...
Страница 26: ...Vertiv SmartRow DCX Installation Manual 26 This page intentionally left blank...
Страница 28: ...Vertiv SmartRow DCX Installation Manual 28 This page intentionally left blank...
Страница 30: ...Vertiv SmartRow DCX Installation Manual 30 This page intentionally left blank...
Страница 32: ...Vertiv SmartRow DCX Installation Manual 32 This page intentionally left blank...
Страница 34: ...Vertiv SmartRow DCX Installation Manual 34 Figure 10 1 Vertiv SmartRow DCX System Submittal Overview typical...
Страница 37: ...Vertiv SmartRow DCX Installation Manual 37 Figure 10 4 Vertiv SmartRow DCX System Submittal Dimensions typical...
Страница 38: ...Vertiv SmartRow DCX Installation Manual 38 Figure 10 5 Vertiv SmartRow DCX System Submittal Clearances typical...
Страница 39: ...Vertiv SmartRow DCX Installation Manual 39 Figure 10 6 Vertiv SmartRow DCX System Submittal One Line typical...
Страница 40: ...Vertiv SmartRow DCX Installation Manual 40 Figure 10 7 Vertiv SmartRow DCX System typical...
Страница 41: ...Vertiv SmartRow DCX Installation Manual 41 Figure 10 8 Vertiv SmartRow DCX Assembly 1 typical...
Страница 42: ...Vertiv SmartRow DCX Installation Manual 42 Figure 10 9 Vertiv SmartRow DCX Assembly 2 typical...
Страница 43: ...Vertiv SmartRow DCX Installation Manual 43 Figure 10 10 Vertiv SmartRow DCX Assembly 3 typical...
Страница 44: ...Vertiv SmartRow DCX Installation Manual 44 Figure 10 11 Vertiv SmartRow DCX Assembly 4 typical...
Страница 45: ...Vertiv SmartRow DCX Installation Manual 45 Figure 10 12 Vertiv SmartRow DCX Fan Control vNSA...
Страница 46: ...Vertiv SmartRow DCX Installation Manual 46 Figure 10 13 Vertiv SmartRow DCX Fan Control vNSA Cabling...
Страница 47: ...Vertiv SmartRow DCX Installation Manual 47 Figure 10 14 Vertiv SmartRow DCX UPS Spacer Kit...
Страница 48: ...Vertiv SmartRow DCX Installation Manual 48 Figure 10 15 Vertiv SmartRow DCX Liebert EXM Installation Pg 1...
Страница 49: ...Vertiv SmartRow DCX Installation Manual 49 Figure 10 16 Vertiv SmartRow DCX Liebert EXM Installation Pg 2...
Страница 50: ...Vertiv SmartRow DCX Installation Manual 50 Figure 10 17 Vertiv SmartRow DCX Liebert EXM Installation Pg 3...
Страница 51: ...Vertiv SmartRow DCX Installation Manual 51 Figure 10 18 Vertiv SmartRow DCX Liebert EXM Installation Pg 4...
Страница 52: ...Vertiv SmartRow DCX Installation Manual 52 Figure 10 19 Vertiv SmartRow DCX Liebert EXM Installation Pg 5...
Страница 61: ...Vertiv SmartRow DCX Installation Manual 61 Figure 10 28 Vertiv SmartRow DCX Racks with Expansion Channels...
Страница 66: ...Vertiv SmartRow DCX Installation Manual 66 Figure 10 33 Vertiv SmartRow DCX Server Rack Isometric Drawing...
Страница 67: ...Vertiv SmartRow DCX Installation Manual 67 Figure 10 34 Vertiv SmartRow DCX Server Rack Outline Drawing...
Страница 68: ...Vertiv SmartRow DCX Installation Manual 68 Figure 10 35 Vertiv SmartRow DCX Network Rack Isometric Drawing...
Страница 69: ...Vertiv SmartRow DCX Installation Manual 69 Figure 10 36 Vertiv SmartRow DCX Network Rack Outline Drawing...
Страница 72: ...Vertiv SmartRow DCX Installation Manual 72 This page intentionally left blank...
Страница 73: ......