2. Modify the Top Plenum PDX/PCW (DCR-A-400PDX):
a. Remove the cover plate on the right-hand side of the Top Plenum-PDX/PCW, Figure 4.3
below, and set it aside to be installed on the top plenum of the final rack on the opposite
end of the row.
b. Move (4) Hex Standoffs from the left-hand side of one of the Top Plenums-Rack
(DCR-A-200) and install them on the right-hand side of the Top Plenum-PDW/PCW
(DCR-A-400PDX), see Figure 4.3 below.
This Top Plenum-Rack without the stand-offs is now the top plenum that will be
positioned on the opposite end of the row with the cover plate installed on its right-hand
side.
3. Continue with the installation procedures, starting with
Install the DCR Base Plenum-PDX/PCW
Figure 4.3 Modifying Top Plenum-PDX/PCW for installation on left-hand side of SmartRow
NO.
DESCRIPTION
NO.
DESCRIPTION
1
Cover plate
3
Top plenum-PDX/PCW after modification
2
Hex stand-off hardware (4 places)
4
Top plenum-PDX/PCW before modification
Vertiv
| SmartRow DCR Installer/User Guide |
17
Содержание SmartRow DCR
Страница 1: ...SmartRow DCR 3 to 6 Rack 20 kW N N 1 and 5 to 10 Rack 36 kW N Cooling Units 60 Hz Installer User Guide...
Страница 6: ...Vertiv SmartRow DCR Installer User Guide 6...
Страница 12: ...Vertiv SmartRow DCR Installer User Guide 12 This page intentionally left blank...
Страница 52: ...Vertiv SmartRow DCR Installer User Guide 52 This page intentionally left blank...
Страница 66: ...Vertiv SmartRow DCR Installer User Guide 66 This page intentionally left blank...
Страница 70: ...Vertiv SmartRow DCR Installer User Guide 70 This page intentionally left blank...
Страница 72: ...Vertiv SmartRow DCR Installer User Guide 72 This page intentionally left blank...
Страница 76: ...Vertiv SmartRow DCR Installer User Guide 76 This page intentionally left blank...
Страница 82: ...Vertiv SmartRow DCR Installer User Guide 82 This page intentionally left blank...
Страница 101: ......