Vertiv
|
NetSure Rectifier Module User Manual (UM1R243000 / 11BJ1307WA)
|
Rev. G
10
•
Typical Input Data (1R242500): 60 Hz Input
a)
System output is initially adjusted to 27.24 volts DC as measured at the system sense points at 50%
of full load and nominal input. “Percent of Full Load” refers to percent of 87.7A at 28.5V.
Nominal
Input
Voltage
Percent
of Full
Load
Input
Current
(Amperes)
Input
VA
Input
Watts
Power
Factor
%
Efficiency
%
Heat
Dissipation
BTU/Hr
208
0
0.3166
65.9478
21.1692
32.1
--
72.23
25
3.376
703.896
696.153
98.9
85.93
334.11
50
6.406
1330.53
1327.87
99.8
90.18
445.11
75
9.495
1973.06
1971.09
99.9
90.84
615.79
100
12.683
2639.33
2636.69
99.9
90.57
848.46
110
13.683
2839.22
2833.54
99.8
90.26
942.01
120
13.69
2846.15
2840.46
99.8
89.74
994.54
240
0
0.3433
82.4263
19.535
23.7
--
66.66
25
2.956
708.258
691.259
97.6
86.51
318.16
50
5.551
1327.8
1322.49
99.6
90.59
424.57
75
8.288
1975.86
1971.91
99.8
91.15
595.74
100
11.054
2625.33
2622.7
99.9
91.07
799.42
110
11.885
2819.12
2816.3
99.9
90.95
869.93
120
11.875
2827.44
2824.61
99.9
90.27
937.98
b)
Maximum Input Current: 15.43A at 100% of full load with output adjusted to 28.5 volts DC as
measured at the shelf output terminals, and input voltage of 180 volts.