200 A Distribution Fuse Panel Assembly Installation & User Manual (UM563317)
|
Rev. B
17
Load Distribution Wiring
WARNING!
Observe proper polarity when making load connections. This panel can be used in +24
VDC or -48 VDC applications. Ensure the proper input voltage is applied to the panel.
NOTE!
Load cannot exceed 60% of device rating at any ambient temperature.
Load and load return leads are connected to screw-type terminal blocks located on the rear of the distribution
fuse panel. Refer to
for terminal block wire size capacity and recommended torque.
The rating of the distribution device determines the wire size requirements. Refer to the American National
Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code
(NEC) and applicable local codes.
Procedure
1.
Remove the rear shields from the distribution fuse panel.
2.
Make load connections as required. See
3.
Record fuse size, location, and other pertinent information on the pull out label located in a slot on the
front of the distribution fuse panel. See
4.
Replace the rear shields onto the distribution fuse panel.
5.
Adhere the appropriate furnished voltage label to the outside of the rear shields as shown in
Содержание NetSure NSFP200