Vertiv
™
NetSure
™
802 and Vertiv
™
NetSure
™
8200 -48 VDC Power System
System Application Guide
Spec. No: 582140000
SAG582140000
Model Nos: 802
NLDB
, 802
NLEB
, 802
NL
-
B
,
Proprietary and Confidential © 2022 Vertiv Group Corp.
Revision BH, September 28, 2022
8200
NLDB
, 8200
NLEB
and 8200
NL
-
B
Page 20
10)
Order AC input lugs as required per
Power/Distribution Bay AC Input, Two (2) Rectifier Feeds Wire Sizes, Branch Circuit
Power/Distribution Bay AC Input, One (1) Rectifier Feed Wire Sizes, Branch Circuit Protection,
in the
ACCESSORY DESCRIPTIONS
section.
11)
Order internal ground busbar assembly, external top-mount battery input busbar assembly, busbar shield kit, external
top-mount ground (load return) busbar assembly, and/or load return lug extension busbar assembly as required per the
appropriate sections located under
12)
If the system is to be connected to an existing system with an MCA, refer to List 64, 65, 66, and 67.
List 3 and 103: Primary Power Only Bay, Five (5) AC Feeds (Common Equipment)
Features
♦
Provides common equipment for one (1) power only bay rated for up to 2200 amperes.
♦
Mounted in a 7’0”H x 24"W x 30"D box framework.
♦
Provides ten (10) rectifier mounting positions.
♦
Provides AC input circuit breakers rated for 22kA interrupting capacity for each rectifier position. Circuit breakers are
pad-lockable.
♦
In ferro replacement applications, will accommodate five (5) AC inputs sized for 400A ferro rectifiers (208V, 100A or
480V, 50A).
♦
List 3: Equipped with an MCA Assembly and provides mounting for optional LMS Main CPU circuit card. Provides a
seven-slot card cage for mounting MCA customer alarm relay circuit cards, MCA I/O circuit cards, and/or optional LMS
I/O circuit cards. Two (2) MCA customer alarm relay circuit cards provided.
♦
List 103: Equipped with an NCU controller and front panel touch screen PC for local access to the NCU webpages.
Includes an IB4 board which provides a Network connection point for NCU remote access. Includes the IB2 NCU
interface board (provides eight (8) programmable form C- relay outputs, eight (8) programmable binary inputs, and two
(2) temperature inputs). Includes the EIB NCU extended interface board (provides five (5) programmable form-C relay
outputs, two (2) temperature inputs, three (3) shunt inputs. and eight (8) battery midpoint inputs).
♦
Expandable either left or right, cable connected.
Restrictions
The system must consist of one (1) primary power/distribution bay or primary power only bay and may consist of up to seven
(7) additional bays. These additional bays may be a combination of secondary power/distribution bays, secondary power only
bays, and/or distribution only bays (maximum of 4 distribution only bays per system).
Requires external main battery termination bars.
Ordering Notes
1)
(208 VAC Input).
2)
If List A specified, bay will include ten (10) P/N 256933200 30 A circuit breakers.
3)
If List B specified, bay will include ten (10) P/N 256937200 60 A circuit breakers.
4)
Order rectifiers as required per
(480 VAC Input) or
(208 VAC Input).
5)
List 3: Order additional MCA customer alarm relay circuit card(s) as required per
, and optional MCA I/O circuit
cards per
. Order optional LMS Monitor and LMS options as required per
, and SAG586505000. Order a
Battery Charge Temperature Compensation Probe as required per
Battery Charge Temperature Compensation Probe for
ACCESSORY DESCRIPTIONS
section.
6)
List 103: Order temperature probes as required per
in the
ACCESSORY DESCRIPTIONS
section.
7)
Order bay grounding lugs as required per
Power Only Bay Frame Grounding Wire Sizes and Lugs
ACCESSORY
DESCRIPTIONS
section.
8)
Order DC output cable lugs as required per
Power Only Bay DC Output Cable Sizes and Lugs
ACCESSORY
DESCRIPTIONS
section.
9)
Order AC input lugs as required per
Power Only Bay AC Input, Five (5) Rectifier Feeds Wire Sizes, Branch Circuit
in the
ACCESSORY DESCRIPTIONS
section.
10)
Order external top-mount battery input busbar assembly, busbar shield kit, external top-mount ground (load return)
busbar assembly, and/or load return lug extension busbar assembly as required per the appropriate sections located
under
11)
If the system is to be connected to an existing system with an MCA, refer to List 64, 65, 66, and 67.